This section describes the IO module registers.
Registers 13824 to 15719 are held by the IO 1.
Registers 16824 to 18719 are held by the IO 2:
oThe registers of the parameters of IO 2 are equal to the registers of the parameters of IO 1 plus 3000.
Example:
oRegister 14599 holds the digital input status register of the IO 1.
oRegister 17599 holds the digital input status register of the IO 2.
oThe order of the registers is the same as that of the IO 1.
oThe characteristics (access type, size, range, and unit) are the same as those of the registers of IO 1.
oRegisters 15360 to 16109 containing the predefined application are specific to the IO 1 because they hold the predefined applications.