The Alarms & History menu contains the following menus:
Level 1 |
Level 2 |
Level 3 |
Function description |
---|---|---|---|
Home |
Alarms & History |
Alarms n |
Displays events of medium and high severity of Entry/Exit type, after the occurrence of the alarm and before the completion. The number n indicates the number of active or held alarms. Trips are not displayed. |
Trips history |
Displays the history of trips, with the date and time that the trip occurred. |
||
Alarms history |
Displays the history of events of medium and high severity, with the date and time for the following type of events: oPulse-type events with the date and time of occurrence oEntry/exit-type events with the date and time of completion Trips are not displayed in this history. |
NOTE: Trip history and alarm history events are listed in chronological order, with the most recent event first.
An alarm screen for an active alarm contains the following information:
![]()
|
Screen title: Alarm Description: up to three lines of text describing the nature of the alarm (medium or high severity event). Event code Event status: Occurrence The date and time that the alarm occurred. |
Use the up and down arrows at the bottom of the screen to navigate between active alarm screens.
A trips history screen contains the following information:
![]()
|
Screen title: Trips history Description: up to three lines of text describing the nature of the trip (high severity event). Event code Event status: Occurrence The date and time that the event occurred. |
Use the up and down arrows at the bottom of the screen to navigate between trips history screens.
An alarms history screen contains the following information:
![]()
|
Screen title: Alarms history Description: up to three lines of text describing the nature of the alarm (medium or high severity event). Event code Event status: oCompleted: for Entry/Exit type events. oOccurrence: for Pulse type events. The date and time that the event completed or occurred. |
Use the up and down arrows at the bottom of the screen to navigate between alarms history screens.