Repair one-line diagrams
Before you repair your project one-line diagrams, back it up.
notice
LOSS of data
Backup your project before you perform a repair.
Failure to follow these instructions can result in corruption of your project.
For more information on correcting one-line errors, see One-line errors and warnings
To repair one-lines:
- In Power Operation Studio: click Launch the Single Line Configuration Utility
.
- Click OK.
- Choose the type of repair you want to perform:
- Repair option alone (Upgrade Project not checked) attempts to fix errors and warnings in a project (used for Power Operation).
- Repair option with Upgrade Project checked is used to upgrade projects from previous versions of the product. This option renumbers all genies in the project. Do not perform this option on a project more than once, and do not perform it on Power Operation 2022 projects.
- Click Repair.
- Click Yes to initiate the repair option that you have selected.
- To save a CSV copy of this summary:
- Click Export.
- At the Save As window, enter a file name and choose the location to save the file.
- Click OK.
The genie information changes, indicating that the repairs have been made.
- Click Save.
- Either click Yes to save the changes to the graphics pages of the project, or click No to cancel the changes.
- Click Export to save a CSV file of these changes.
- Click OK to exit the summary window and return to the One-Line Configuration Utility window.
- Compile the project and then run it.
Genie information for the selected project displays. For descriptions of the fields on this page, see Reviewing Genie Configurations.
NOTE: When two busbars have the same line active, they are assigned the same busbar number.
The following table describes the repairs made in each option.
Genie Type |
Repair |
Repair— Upgrade Project |
---|---|---|
Breaker |
Breaker Number |
ALL Breaker Numbers |
Sources |
Source Number Line Active |
ALL Source Numbers Line Active |
Meters |
Meter Number Line Active |
ALL Meter Numbers Line Active |
Transformers |
Sim Source Numbers (top and bottom) |
Sim Source Numbers (top and bottom) |
Busbars |
---- |
All valid busbars will be reassigned, including destination and source busbars for breakers and transformers |
A message describes the degree of repair that is about to take place.
Each message states that graphics pages will not be modified by the repair process. This means that the repairs will not be applied to your project graphics pages until you click Save.
A Repair Summary window displays, listing the repairs that have been initiated.
The Save window appears. This is where the changes are saved to your project.
If you click Yes: The changes are saved to the project. For a large project, this might take several minutes. When the repairs are saved to the project, a Save Summary window appears listing the repairs that were made and saved.
If you click No: Click Close, then click No when you are asked whether you want to save the modified project.
It is possible that some errors and warnings will not be repaired, for example, missing busbar numbers or missing equipment. Click individual errors or warnings to view them (note that the warning and error icons include a tooltip to tell you what is wrong). Note the missing information, then go to the graphics builder and make the necessary changes.