Citect.ini parameters in 7.20
This topic lists the parameters that have been added or changed in version 7.20 of Power Operation Expert.
It includes:
New Parameters
The following parameters are new in version 7.20 . For an entire list of the system parameters, refer to the Parameters documentation.
Alarm Parameters
[Alarm.ClusterName.ServerName]DisableConnection |
Specifies if a client will not connect to a server. |
[Alarm.ClusterName.ServerName]Priority |
Specifies the client priority for the server connection. |
[Alarm]ReloadBackOffTime |
Back-off time configured to control the pace of the reload on an alarm server. |
Client Parameters
[Client]AutoLoginClearPassword |
When set to 1 the cache is cleared of any client login credentials for consistency with the [Server]AutoLoginClearPassword ini parameter. |
[Client]DisableDisplay |
Sets whether to allow the client process to run in the background without a visible window. |
[Client]EvictTimeout |
Sets the amount of time a tag reference is cached before it is evicted. |
[Client]PartOfTrustedNetwork |
Tells a Client process to attempt to authenticate using the stored server password. It is automatically set by the Setup Wizard. |
[Client] StalenessPeriod |
Number of seconds to use for tag staleness period. |
[Client]StalenessPeriodTolerance |
Staleness period tolerance |
CtAPI Parameters
[CtAPI]RoundToFormat |
Indicates to the user if values rounded to format. |
CtDraw.RSC Parameters
[CtDraw.RSC]AllowEditSuperGeniePage |
When set enables the user to choose whether or not to open and edit a Super Genie page. |
CtEdit Parameters
[CtEdit]CompileSuccessfulCommand |
Indicates to the compiler an optional command, script or batch file to execute after a successful compile. |
[CtEdit]CompileUnsuccessfulCommand |
Indicates to the compiler an optional command, script or batch file to execute after an unsuccessful compile. |
[CtEdit]Starter |
Specifies the directory where the starter projects are located. |
Debug Parameters
[Debug]ArchiveFiles |
Archives log files once the size specified by [Debug]MaximumFileSize is reached. |
[Debug]CategoryFilter |
Lets you filter logging messages by component category. |
[Debug]CategoryFilterMode |
Enables logging of categories declared by the [Debug]CategoryFilter value. |
[Debug]EnableLogging |
Enables or disables the logging mechanism. |
[Debug]MaximumFileSize |
Sets the maximum size for a log file. |
[Debug]Priority |
Lets you filter logging messages according to their priority. |
[Debug]SeverityFilter |
Lets you filter logging messages according to their severity. |
[Debug]SeverityFilterMode |
Enables logging of severities declared by the [Debug]SeverityFilter value. |
General Parameters
[General]MiniumlUpdateRate |
Specifies the time period (sec) at which a DataSource will send tag update value notifications to the subscription clients. |
[General]StalenessPeriod |
Specifies the time period (sec) after which a tag value is considered to be “stale” if it was not updated during this period. |
IOServer Parameters
[IOServer]EnableEventQueue |
Enables the event queue. |
[IOServer]MaxEventsDrop |
Sets the number of events that are dropped when too many are queued. |
[IOServer]MaxEventsQueued |
Sets the total number of events that can be queued. |
[IOServer]MaxTimeInQueueMs |
Sets the total time for which an event can be queued. |
LAN Parameters
[LAN]AllowRemoteReload |
Enables remote reloading of servers from a client. |
[LAN]ClientRetryTime |
Sets the length of time between connection attempts by a client. |
[LAN]EarliestLegacyVersion |
Specify the minimum legacy version from which the current version will accept connections. |
[LAN]HighWaterMark |
The number of messages waiting to be sent on a particular network connection at which the high water mark event will occur. |
[LAN]KeepAliveInterval |
Sets the length of time between two keep alive transmissions by the client. |
[LAN]KeepAliveTime |
Sets the length of time between two keep alive transmissions in idle conditions. |
[LAN]ListenerRetryTime |
Sets the length of time a server waits between attempts to listen for a client connection. |
[LAN]LowWaterMark |
After the high water mark has been reached on a particular network connection, the low water mark represents the number of messages waiting to be sent at which we will resume normal operations. |
[LAN]NoSocketDelay |
Switches off the delay on a socket caused by the use of the Nagle algorithm. |
[LAN]ReadOnlyLegacyConnections |
When set to 1 version 7.10 clients can only communicate in read-only mode.This parameter overrides 'EarliestLegacyVersion' . |
Multi-Monitor Parameters (CSV Include project)
[MultiMonitor]DisableAutoStart |
Disables the new multi-monitor functionality. |
Page Parameters
[Page]AddDefaultMenu |
Determines whether to add the default menu items to the tabbed menu bar. |
[Page]BadDitheringColor |
Sets the dithering color for graphics elements which are dithered if the value quality is “bad”. |
[Page]BadDitheringDensity |
Sets the dithering density for graphics elements which are dithered if the value quality is “bad”. |
[Page]BadText |
Text Objects can be displayed as #COM type errors, or as the text overlaid with a dithered pattern if the ‘display value’ expression has “bad” quality. |
[Page]BadTextBackgroundColor |
Sets the background color for numeric / text graphics objects to indicate “bad” quality. |
[Page]EnableQualityToolTip |
Set by default it controls the quality tooltip |
[Page]ErrorDitheringColor |
Sets the dithering color for graphics elements which are dithered if an internal error occurs. |
[Page]ErrorDitheringDensity |
Sets the dithering density for graphics elements which are dithered if an internal error occurs. |
[Page]ErrorTextBackgroundColor |
Sets the background color for numeric / text graphics objects to indicate an internal error. |
[Page]IgnoreValueQuality |
Defines the value quality handling by graphics pages. |
[Page]OverrideDitheringColor |
Sets the dithering color for graphics elements which are dithered if their values are override (“forced”). |
[Page]OverrideDitheringDensity |
Sets the dithering density for graphics elements which are dithered if an internal error occurs. |
[Page]OverrideTextBackgroundColor |
Sets the background color for numeric / text graphics objects to indicate that the value presented on the objects is override (“forced”). |
[Page]ShowBadText |
Text Objects can be displayed as #BAD text, or as the text overlaid with a dithered pattern if the "display value" expression has “bad” quality. |
[Page]ShowErrorText |
Text Objects can be displayed as #COM type errors, or as the text overlaid with a dithered pattern if the ‘display value’ expression has “uncertain” quality. |
[Page]ShowUncertainText |
Text Objects can be displayed as #UNC text, or as the text overlaid with a dithered pattern if the "display value" expression has “uncertain” quality. |
[Page]Splash |
Specify the name of the Splash Screen page. |
[Page]SplashTimeout |
Time in milliseconds for the Splash Screen to display. |
[Page]SplashWinName |
Specify the label of the Splash Window for use with the Cicode function WinNumber(). |
[Page]StartupDelay |
Milliseconds between when Splash Screen and Start Screen are displayed. |
[Page]StartupHeight |
Height of the Start Page on main display monitor. |
[Page]StartupMode |
Mode of Start Page on main display monitor. |
[Page]StartupWidth |
Width of the Start Page on main display monitor. |
[Page]StartupWinName |
Specify the label of the Start Window for use with the Cicode function WinNumber(). |
[Page]StartupX |
X coordinate of Start Page on main display monitor. |
[Page]StartupY |
Y coordinate of Start Page on main display monitor. |
[Page]UncertainDitheringColor |
Sets the dithering color for graphics elements which are dithered if the value quality is “uncertain”. |
[Page]UncertainDitheringDensity |
Sets the dithering density for graphics elements which are dithered if the value quality is “uncertain”. |
[Page]UncertainText |
Text Objects can be displayed as #COM type errors, or as the text overlaid with a dithered pattern if the ‘display value’ expression has “uncertain” quality. |
[Page]UncertainTextBackgroundColor |
Sets the background color for numeric / text graphics objects to indicate “uncertain” quality. |
[Page]WaitForValidData |
Specifies whether the animation system will attempt to wait for valid data from subscriptions necessary to draw a graphics page before it is animated. |
Report Parameters
[Alarm.ClusterName.ServerName]DisableConnection |
Specifies if a client will not connect to a server. |
[Alarm.ClusterName.ServerName]Priority |
Specifies the client priority for the server connection. |
Runtime Manager Parameters
[RuntimeManager]AllowReload |
Enables or disables the reload option in the Runtime Manager menu. |
Security Parameters
[Security]DisableDEP |
Set to turn off DEP protection for the Power Operation Runtime. |
Server Parameters
[Server]AutoLoginMode |
Determines the auto login method the server will use when establishing connections to other servers. |
Trend Parameters
[Trend]AcquisitionTimeout |
Sets a timeout to stop a trend server infinitely acquiring a valid data sample from an I/O device. |
[Trend.ClusterName.ServerName]DisableConnection |
Specifies if a client should not connect to a server. |
[Trend.ClusterName.ServerName]Priority |
Specifies the client priority for the server connection. |
[Trend]ReloadBackOffTime |
Back-off time configured to control the pace of the reload on an Trend server. |
Modified Parameters
CtEdit Parameters
[CtEdit]Copy |
Supports runtime changes, it enables you to switch the SCADA node to use a new runtime configuration by pointing to a new location. |
Re-instated Parameters
IOServer Parameters
[IOServer]BlockWrites |
Determines whether Power Operation will try to block optimize writes to I/O devices. |
Obsolete Parameters
AnmCursor Parameters
[IOServer]BlockWrites |
Determines whether Power Operation will try to block optimize writes to I/O devices. |
General Parameters
[General]TagAssMode |
Validates the tag name in the Association Function. Refer to [General]TagDB instead.
|
LAN Parameters
[LAN]AllowLegacyConnections |
Set to allow previous versions of client to connect to the server. Replaced with [LAN]EarliestLegacyVersion and the new trusted network authentication between SCADA servers. The Setup Wizard now allows a system password to be set on each server on your network. |
[LAN]ServerLoginEnabled |
Set to disable default server login. Replaced with [LAN]EarliestLegacyVersion and the new trusted network authentication between SCADA servers. The Setup Wizard now allows a system password to be set on each server on your network. |
Page Parameters
[Page]BackgroundColour |
Replaced with [Page]BackgroundColor. Specifies the color used to fill in the background when a page is smaller than the minimum width of a window. |
[Page]ComBreak |
Determines whether an error status is displayed on the screen if a communication error occurs. Replaced with new page quality settings such as [Page]IgnoreValueQuality, [Page]BadText,[Page]BadDitheringDenisty. |
[Page]ComBreakText |
Determines the display of text objects if a communication error occurs that affects the text. Replaced with new page quality settings such as [Page]IgnoreValueQuality, [Page]BadText,[Page]BadDitheringDenisty. |
[Page]DynamicComBreakColour |
Replaced with [Page]DynamicComBreakColor. Sets the color of the ComBreak dithering. |
[Page]DynamicComBreakDensity |
Sets the density of the ComBreak. Replaced with new page quality settings such as [Page]IgnoreValueQuality, [Page]BadText,[Page]BadDitheringDenisty. |
Time Parameters
[Time]Deadband |
The deadband time checked by the Time Server before it adjusts the time on the client(s). |
[Time]Disable |
Enables/disables the processing of time messages from the Time Server. |
[Time]Name |
Enables the time synchronization functionality. |
[Time]PollTime |
The period that the Time Server uses to synchronize other Power Operation computers on the network. |
[Time]RTsync |
Determines whether the Time Server will synchronize with the hardware clock. |
[Time]Server |
Determines whether this computer is a Time Server. |
Trend Parameters
[Trend]CursorColour |
Replaced with [Trend]CursorColor. Allows the cursor color to be specified. |