|
READS
|
|
Invalid Block
(L:P:0)
|
IB
|
LONG
|
Up to 1,000 sequential registers
|
No
|
Generic only
|
Defines invalid blocks of memory in the device. The driver does not include these registers in block reads.
|
|
Date / Time (L:P:1) (3 register)
|
UT
|
LONG
|
3 sequential registers
|
No
|
Generic – if it fits
|
Register N:
High byte = Month 1–12 Low byte = Day 1–31
Register N+1:
High byte = Year 0–199 (+1900)
Low byte = Hour 0–23
Register N+2:
High byte = minutes 0–59 Low byte = seconds 0–59
|
|
Date / Time (L:P:2) (6 register)
|
UT
|
LONG
|
6 sequential registers
|
No
|
Generic
– if it fits
|
Register N: Seconds 0–59
Register N+1: Minutes 0–59
Register N+2: Hours 0–23
Register N+3: Day 1–31
Register N+4: Month 1–12
Register N+5: Year 0–199 (+1900)
|
|
Date / Time (L:P:3) (3 or 4 register --Circuit Monitor/ Power Meter)
|
UT
|
LONG
|
3 or 4 sequential registers
|
No
|
CM/PM
|
Register N:
High byte = Month 1–12, Low byte = Day 1–31
Register N+1:
High byte = Year 0–199 (+1900)
Low byte = Hour 0–23
Register N+2:
High byte = minutes 0–59 Low byte = seconds 0–59
Register N+3:
msec = 0–999 (unused)
|
|
Date / Time (L:P:4) (3 or 4 registers SEPAM)
|
UT
|
LONG
|
3 or 4 sequential registers
|
No
|
SEPAM
|
Register N:
Bits 0–6 = Year: 0 –70 (2000– 2070)
71 – 99 (1971–1999)
Register N+1:
Bits 8-11 = Month
Bits 0-4 = Day
Register N+2:
Bits 8-12 = Hour
Bits 0-5 = Minutes
Register N+3: msec = 0-59,999 (seconds are ms/1000)
|
|
Date/Time
(L:P:5)
3-register Micrologic
|
UT
|
LONG
|
3 sequential registers
|
No
|
micro
|
Register N:
High byte = Month 1–12, Low byte = Day 1–31
Register N+1:
High byte = Year 0–69 (+2000), Year 70–99 (+1900)
Low byte = Hour 0–23
Register N+2:
High byte = minutes 0–59 Low byte = seconds 0–59
|
|
Date/Time
(L:P:6)
4-register Micrologic
|
UT
|
LONG
|
4 sequential registers
|
No
|
micro
|
Register N:
High byte = Month 1–12, Low byte = Day 1–31
Register N+1:
High byte = Year 0–69 (+2000), Year 70–99 (+1900)
Low byte = Hour 0–23
Register N+2:
High byte = minutes 0–59 Low byte = seconds 0–59
Register N+3:
msec = 0–999 (unused)
|
|
Date/Time
(L:P:7)
3-register Argos
|
UT
|
LONG
|
3 sequential registers
|
No
|
Argos
|
The number of seconds since 01/01/2000 (00:00:00)
register 1 = MSB
register 2 = LSB
register 3 = milliseconds
|
|
Date/Time
(L:P:8)
4-register IEC 870-5-4
|
UT
|
LONG
|
4 sequential registers
|
No
|
generic
|
Register N:
Bits 0–6 = Year: 0 –127 (2000– 2127)
Register N+1:
Bits 8-11 = Month
Bits 0-4 = Day
Register N+2:
Bits 8-12 = Hour
Bits 0-5 = Minutes
Register N+3: msec = 0-59,999 (seconds are ms/1000)
|
|
Modulo 10k (L:P:10)
|
BC
|
STRING
|
Up to 4 registers
|
No
|
generic
|
Result is a string representation.
Range is 0 to 9,999,999,999,999,999
Each register has a range of 0 to 9,999
Result is: – R4*10,000^3 + R3*10,000^2 + R2*10,000 + R1
|
|
Modulo 10k Val
(L:P:11)
|
BC
|
REAL
|
Up to 4 registers
|
No
|
generic
|
Result is a string representation.
Range is 0 to 9,999,999,999,999,999
Each register has a range of 0 to 9,999
Result is: – R4*10,000^3 + R3*10,000^2 + R2*10,000 + R1
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Modulo 10k Energy
(L:P:12)
|
BC
|
STRING
|
Up to 4 registers
|
No
|
generic
|
Result is a string representation.
Range is 0 to 9,999,999,999,999.9
Each register has a range of 0 to 9,999
Result is – (R4*10,000^3 + R3*10,000^2 + R2*10,000 + R1)/1000
|
|
Modulo 10k Energy Val
(L:P:13)
|
BC
|
REAL
|
Up to 4 registers
|
No
|
generic
|
Result is a string representation.
Range is 0 to 9,999,999,999,999.9
Each register has a range of 0 to 9,999
Result is – (R4*10,000^3 + R3*10,000^2 + R2*10,000 + R1)/1000
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
PL Digital Input SS
(L:P:20)
|
SS
|
LONG
|
2 registers
|
No
|
CM/PM
|
First register (100–199 inclusive) indicates that this is a digital input register.
Second register is masked to test for either one 1 or one 0.
Result is: 0 = off and 1 = on.
This result can be inverted.
|
|
PL Digital Input DS
(L:P:21)
|
DS
|
LONG
|
2 registers
|
No
|
CM/PM
|
Same as PL Digital Input SS except:
Result is 0 = intermediate, 1 = off, 2 = on, 3 = bad-state.
Inversion will invert only off and on states.
|
|
PL Digital Input TF
(L:P:22)
|
SS
|
DIGITAL
|
2 registers
|
No
|
CM/PM
|
Same as PL Digital Input SS except:
Result is: 0 = false and 1 = true.
This result can be inverted.
|
|
PL Digital Output SS
(L:P:23)
|
SS
|
LONG
|
2 registers
|
No
|
CM/PM
|
First register (200–299 inclusive) indicates that this is a digital output register.
Second register is masked to test for either one 1 or one 0.
Result is: 0 = off and 1 = on.
This result can be inverted.
|
|
PL Digital Output DS
(L:P:24)
|
DS
|
LONG
|
2 registers
|
No
|
CM/PM
|
Same as PL Digital Output SS, except:
Result is: 0 = intermediate, 1 = off, 2 = on, 3 = bad-state.
Inversion will invert only off and on states.
|
|
PL Digital Output TF
(L:P:25)
|
SS
|
DIGITAL
|
2 registers
|
No
|
CM/PM
|
Same as PL Digital Output SS except:
Result is: 0 = false and 1 = true.
This result can be inverted.
|
|
Status SS (L:P:26)
|
SS
|
LONG
|
Up to 4 registers
|
No
|
Generic
|
Each register is compared to a ones’ mask. Optionally it can be compared to a zeros’ mask. (Use the Edit Address screen in the Profile Editor to create masks for the user.)
Result is: 0 = off and 1 = on.
If there is only one register, the result can be inverted.
|
|
Status OR SS
(L:P:226)
|
SS
|
LONG
|
2 to 4 registers
|
No
|
Generic
|
Each register is compared to a ones’ mask. These results are OR’ed together. Optionally, it can be compared to a zeros’ mask. (Use the Edit Address screen in the Profile Editor to create masks for the user.)
Result is: 0 = off and 1 = on.
|
|
Status DS (L:P:27)
|
DS
|
LONG
|
Up to 4 registers
|
No
|
Generic
|
Same as Status SS except:
Result is: 0 = intermediate, 1 = off, 2 = on, 3 = bad-state.
Inversion will invert only off and on states.
|
|
Status OR DS
(L:P:227)
|
DS
|
LONG
|
2 to 4 registers
|
No
|
Generic
|
Same as Status OR SS except:
Result is: 0 = intermediate, 1 = off, 2 = on, 3 = bad-state.
|
|
Status TF (L:P:28)
|
SS
|
DIGITAL
|
Up to 4 registers
|
No
|
Generic
|
Same as Status SS except:
Result is: 0 = false and 1 = true.
This result can be inverted.
|
|
Status OR TF
(L:P:228)
|
SS
|
DIGITAL
|
2 to 4 registers
|
No
|
Generic
|
Same as Status OR SS except:
Result is: 0 = false and 1 = true.
|
|
Status Int (L:P:29)
|
BC
|
LONG
|
1 register
|
No
|
CM/PM
|
One register is bit anded with one mask. The result will be an integer that can be used to choose the appropriate enumeration.
|
|
Status Enumeration
(L:P:229)
|
EN
|
LONG
|
1 to 4 registers
|
No
|
Generic
|
Each register is compared to a ones’ mask. Optionally it can be compared to a zeros’ mask. (Use the Edit Address screen in the Profile Editor to create masks for the user.)
Result is a combination of the results for each register, using this formula:
result for register 1 * 2^0 + result for register 2 * 2^1 + result for register 3 * 2^2 + result for register 4 * 2^3
|
|
PL Analog Input
(L:P:30)
|
MV/CM
|
REAL
|
3 registers
|
No
|
CM/PM
|
First register (300–399 inclusive) indicates that this is an analog input register.
Second register is treated as a signed value.
Third register can contain a value from –3 to 3 and will be used to scale the second register (R2*10^R3).
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Breaker Rack Status
(L:P:230)
|
EN
|
LONG
|
2 to 3 registers
|
No
|
Generic
|
Register 1 = breaker racked in
Register 2 = breaker racked out
Register 3 = breaker in test (optional)
Results:
0 = racked in
1 = racked out
2 = test
3 = error
4 = in between positions
|
|
PL Analog Output
(L:P:31)
|
MV/CM
|
REAL
|
2 registers
|
No
|
CM/PM
|
First register (400–499 inclusive) indicates that this is an analog output register.
Second register is treated as a signed value.
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Scaled Register Signed
(L:P:32)
|
MV/CM
|
REAL
|
1 or 2 registers
|
Either
(optional)
|
Generic
|
For a single register: treated as a signed value from –32,767 to +32,767. (-32768 will result in a NA)
For two registers: the registers will be concatenated together, the first register filling bits 16–32 and the second register filling bits 0–15. Values will range from
–2,147,483,648 to –2,147,483,647.
Values can be scaled using a fixed scale or a scale register.
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Scaled Register Unsigned
(L:P:33)
|
MV/CM
|
REAL
|
1 to 4 registers
|
Either
(optional)
|
Generic
|
For a single register: treated as an unsigned value from 0 to 65,535.
For two registers: the registers will be concatenated together, the first register filling bits 16–32 and the second register filling bits 0–15. Values will range from
0 to 4,294,967,295.
Values can be scaled using a fixed scale or a scale register.
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Scaled Register Signed No NA
(L:P:34)
|
MV/CM
|
REAL
|
1 or 2 registers
|
Either
(optional)
|
Generic
|
Same as Scaled Register except that a single register with value -32768 is acceptable and will be reported as such.
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Scaled Register Signed SEPAM A
(L:P:35)
|
MV/CM
|
REAL
|
2 registers
|
Either
(optional)
|
Generic
|
Same as Scaled Register except that 0xFFFFFFFF or 0x00007FFF will be NA.
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Scaled Register Signed SEPAM B
(L:P:36)
|
MV/CM
|
REAL
|
2 registers
|
Either
(optional)
|
Generic
|
Same as Scaled Register except that 0xFFFFFFFF will be NA.
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
IEEE 32 Real
(L:P:37)
|
MV/CM
|
REAL
|
2 sequential registers
|
No
|
Generic
|
Uses the IEEE standard for floating-point arithmetic (IEEE 754);
register 1 is MSB, register 2 is LSB
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Scaled Register Signed SEPAM 2000 Format B
(L:P:38)
|
MV/CM
|
REAL
|
1 register
|
Either
(optional)
|
Generic
|
For a single register: treated as a signed value from –32,767 to +32,767:
From the value of the unsigned register, subtract 32768; then apply the scale.
0000 or FFFF will be NA.
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
PL String (L:P:39)
|
ST
|
STRING
|
1 to 10 sequential registers
|
No
|
Generic
|
Each register can represent up to two ASCII characters.
|
|
Sum Registers (L:P:40)
|
MV/CM
|
REAL
|
1 to 4 registers
|
Either
(required)
|
Generic
|
Result is:
R1 + … + Rn * 10^scale
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Divide Registers
(L:P:41)
|
MV/CM
|
REAL
|
3 registers
|
Either
(required)
|
Generic
|
Result is:
R1/R2 * R3 * 10^scale
If R2 is zero, result will be #COM
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Multiply Registers
(L:P:42)
|
MV/CM
|
REAL
|
1 to 4 registers
|
Either
(required)
|
Generic
|
Result is:
R1 * … * Rn * 10^scale
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Average Registers
(L:P:43)
|
MV/CM
|
REAL
|
1 to 4 registers
|
Either
(required)
|
Generic
|
Result is:
Avg(R1 … Rn) * 10^scale
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Average Registers WF
(L:P:44)
|
MV/CM
|
REAL
|
2 to 4 registers
|
Either
(required)
|
Generic
|
Result is:
Avg(R1 … Rn-1) * Rn * 10^scale
NOTE: This logic code (as with all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Sum with Scale
(L:P:45)
|
MV/CM
|
REAL
|
2 registers
|
Either
(required)
|
CM/PM
|
Result is:
(R1 * 10^scale) + R2
NOTE: This logic code (as with all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Sum with Scale Unsigned (L:P:46)
|
MV/CM
|
REAL
|
2 registers
|
Either
(required)
|
CM/PM
|
Result is same as previous, except unsigned.
NOTE: This logic code (as with all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Vector Math
(L:P:47)
|
MV/CM
|
REAL
|
2 registers
|
Either (required)
|
Generic
|
Result is:
sqrt (R1^2 + R2^2) x scale
NOTE: This logic code (as with all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Vector Math IEEE
(L:P:48)
|
MV/CM
|
REAL
|
4 registers
|
Either (required)
|
Generic
|
Result is:
sqrt ([R1 R2]^2 + [R3 R4]^2) x scale
where [ ] indicates IEEE32 representation
NOTE: This logic code (as with all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Multiply Registers 32-bit
(L:P:49)
|
MV/CM
|
REAL
|
3 or 4 registers
|
Either (optional)
|
Generic
|
Result is:
[R1R2] * [R3(R4)],
meaning Regs 1 and 2 are a 32 bit number.
The number is multiplied by Reg 3 (if 16 bit) or Reg 3 and 4 (32 bit number)
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
CM4 Power Factor IEEE
(L:P:50)
|
MV/CM
|
REAL
|
1 register
|
No
|
CM4
|
Returns the IEEE power factor.
|
|
PM8 Power Factor IEEE
(L:P:51)
|
MV/CM
|
REAL
|
1 register
|
No
|
PM8
|
Returns the IEEE power factor (converted from IEC mode as necessary).
The device may be in IEEE or IEC mode if the device firmware version is 11.6 or higher. If the device firmware version is below 11.6, IEC mode is not supported.
NOTE: This logic code (as with all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
SP40 Power Factor IEEE
(L:P:52)
|
MV/CM
|
REAL
|
1 register
|
No
|
SEPAM 40
|
Returns the IEEE power factor (converted from IEC mode).
NOTE: This logic code (as with all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
ML Power Factor IEEE
(L:P:53)
|
MV/CM
|
REAL
|
2 registers
|
No
|
ML
|
Returns the IEEE power factor (converted from IEC mode as necessary).
The second input register must be the associated Reactive Power for the Power Factor requested.
NOTE: This logic code (as with all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Generic Power Factor
(L:P:54)
|
MV/CM
|
REAL
|
2 registers
|
No
|
Generic
|
R2/sqrt (R2^2 + R1^2)
where:
R2 = real power R1 = reactive power
NOTE: This logic code (as with all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Generic Power Factor - IEEE32 variation
(L:P:55)
|
MV/CM
|
READ
|
4 registers
|
No
|
Generic
|
[R3 R4]/
sqrt ([R3 R4]^2 + [R1 R2]^2)
where:
R3 = real power IEEE32 MSR
R4 = real power IEEE32 LSR R1 = reactive power IEEE32 MSR
R2 = reactive power IEEE32 LSR
|
|
SP2000 Power Factor IEEE
(L:P:56)
|
MV/CM
|
REAL
|
1 register
|
No
|
SEPAM 2000
|
Returns the IEEE power factor (converted from IEC mode).
NOTE: This logic code (as with all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Scaled Register Signed 64-bit
(L:P:57)
|
MV/CM
|
REAL
|
4 registers
|
Either
(optional)
|
Generic
|
Reads a 64-bit signed integer and returns a REAL value.
NOTE: This logic code (as with all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
Power Factor IEEE
(L:P:58)
|
MV/CM
|
REAL
|
2 registers
|
No
|
Generic
|
Takes a 4 quadrant power factor (IEEE32 real) and returns an IEEE power factor.
|
|
IEEE 64-bit double
(L:P:59)
|
MV/CM
|
REAL
|
4 registers
|
No
|
Generic
|
Uses the IEEE standard for floating-point arithmetic (IEEE 754); returns the value as 32-bit REAL.
NOTE: This logic code (as with all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
IEEE 64-bit double
(L:P:60)
|
MV/CM
|
STRING
|
4 registers
|
No
|
Generic
|
Uses the IEEE standard for floating-point arithmetic (IEEE 754); returns the value as 64-bit STRING.
NOTE: This logic code (as with all REAL logic codes) has an accuracy of 15 digits. Anything longer than 15 digits should not be considered accurate.
|
|
WRITES (these are write-only; see below for Read/Write codes)
NOTE: If the device is capable of preventing (blocking) writes to its registers, verify that the "block" feature is disabled before you implement the write.
|
|
Status Write Register
(L:P:101)
|
SS
|
LONG
|
1 register
|
No
|
Generic
|
If you input 1 to this tag it will write the MASK value to the register.
|
|
Status Write Register AND
(L:P:102)
|
SS
|
LONG
|
1 register
|
No
|
Generic
|
If you input 1 to this tag it will read the register and AND the MASK with the register (This puts a 0 wherever there is a 1 in the mask and leaves the rest alone).
|
|
Status Write Register OR
(L:P:103)
|
SS
|
LONG
|
1 register
|
No
|
Generic
|
If you input 1 to this tag it will read the register and OR the MASK with the register (This puts a 1 wherever there is a 1 in the mask and leaves the rest alone).
|
|
Write Register Unsigned
(L:P:110)
|
MV/CM
|
REAL
|
1 register
|
Either
|
Generic
|
This will take the input value read in and divide out the scale factor and the conversion factor. It will then round to the nearest whole number and if it is a value from 0 to 65535 it will put this value in the register.
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
| Write Register Signed (L:P:111) |
MV/CM
|
REAL
|
1 register
|
Either
|
Generic
|
This will take the input value read in and divide out the scale factor and the conversion factor. It will then round to the nearest whole number and convert the signed value to an unsigned value from 0 to 65535. It will put this value in the register.
NOTE: This logic code (and all REAL logic codes) has an accuracy of seven digits. Anything longer than seven digits should not be considered accurate.
|
|
READ/WRITES
|
|
Read/Write Holding Register
(L:P:120)
|
MV/CM
|
LONG
|
1 register
|
No
|
Generic
|
You can write any value from 0 to 65535 and read an unsigned value from the same register.
|
|
Read/Write Coil Register
(L:P:121)
|
SS
|
DIGITAL
|
1 register
|
No
|
Generic
|
You can write 0 or 1 and read a value from the same register.
|
|
READ
|
|
Command Read Date/Time
(L:P:170)
|
CR
|
LONG
|
2 to 4 registers
|
No
|
MicrologicX
|
Register 1: <Command ID>:<Module>
Register 2: <Register>:<# of registers>
Register 3: <# of parameters>:<Parameter 1>
Register 4: <Parameter 2>:<Parameter 3>
If there are no parameters needed, omit registers 3 and 4.
All registers formatted as <Decimal>:<Hexadecimal>
|
|
Command Read IEEE32
(L:P:171)
|
CR
|
REAL
|
2 to 4 registers
|
Fixed
|
MicrologicX
|
Register 1: <Command ID>:<Module>
Register 2: <Register>:<# of registers>
Register 3: <# of parameters>:<Parameter 1>
Register 4: <Parameter 2>:<Parameter 3>
If there are no parameters needed, omit registers 3 and 4.
All registers formatted as <Decimal>:<Hexadecimal>
|
|
Command Read Scaled Signed
(L:P:172)
|
CR
|
REAL
|
2 to 4 registers
|
Fixed
|
MicrologicX
|
Register 1: <Command ID>:<Module>
Register 2: <Register>:<# of registers>
Register 3: <# of parameters>:<Parameter 1>
Register 4: <Parameter 2>:<Parameter 3>
If there are no parameters needed, omit registers 3 and 4.
All registers formatted as <Decimal>:<Hexadecimal>
|
|
Command Read Scaled Unsigned
(L:P:173)
|
CR
|
REAL
|
2 to 4 registers
|
Fixed
|
MicrologicX
|
Register 1: <Command ID>:<Module>
Register 2: <Register>:<# of registers>
Register 3: <# of parameters>:<Parameter 1>
Register 4: <Parameter 2>:<Parameter 3>
If there are no parameters needed, omit registers 3 and 4.
All registers formatted as <Decimal>:<Hexadecimal>
|
| COMMAND READ/ WRITE |
|
PL String
(L:P:175)
|
CR |
STRING |
1 to 40 Sequential Registers |
No |
HDPM |
Register 1: <Channel Name/Rack ID>:<Module>
Register 2: <Starting Register Address>:<Number of Sequential Registers>
NOTE: Module value will be 0. This logic code is used for command read and write value to Circuit label and Rack ID of HDPM Device.
|
|
Date/Time
(L:P:176)
|
UT |
LONG |
2 Sequential Registers |
No |
HDPM |
Register 1: Least Significant Bit.
Register 2: Most Significant Bit
NOTE: This logic code read the value in Epoc Format. (The resulting value will be represented in seconds.)
|