Managing IEC 61850 datasets

Use this screen to add and edit IEC 61850 tag datasets to a profile.

To access this screen:

  1. Display the Create Device Profiles tab for a device that includes ICD files.
  2. Select the Parameters sub-tab, then select Edit on the DataSets line.

NOTE: Not all ICD files allow you to add, edit, or delete datasets. If all fields are greyed out, you will not be able to change the set.

In the upper left corner are the device profile name and device type names that come from an imported ICD file. All of the entry fields are initially greyed-out. The device type datasets (upper box) are resident in the ICD. The device profile datasets (lower box) have been created or copied from other datasets in the device type or device profile.

Creating a new dataset

  1. Select Create New beside the Device Profile DataSets box.

    The fields on the right side of the screen are enabled.

  2. Type a name and description for the new dataset. These are free-form fields, but they must comply with IEC 61850 standards.
  3. Choose the appropriate logical device, then choose the logical node for that device.
  4. Choose the functional constraint for the content. This will filter the display of device type objects/topics in the box below.

    When you choose All, you must then choose an object that already has a functional constraint in it. If you choose a specific constraint, the list of available objects is filtered to display only those that include that constraint.

  5. From the Device Type Objects, choose the appropriate objects for this profile.
  6. Select OK.

The new dataset is added in the lower left, to the Device Profile list.

Creating a dataset from an existing dataset

You can create a new dataset either from one that resides in the ICD (from the device type) or from the device profile.

To create a dataset from another block:

  1. Select the dataset (either device type or device profile) to be used as the starting point for the new dataset. 
  2. Select Create From.
  3. Make the appropriate changes. You must change the name. All datasets in a single profile must have unique names.
  4. Select OK.

The new name displays under the Device Profile List.

Copying a dataset to a Device Type

This feature will not typically be used. If, however, you delete a dataset from the device type, but later decide you want to add it back, follow this procedure. (You cannot delete datasets that are used by a report control block.)

  1. From the Device Type DataSets box, highlight the dataset you want to add back.  
  2. Select Copy To.

The dataset displays under the Device Type list in the Device Profile DataSets.

Editing and deleting datasets

You cannot edit or delete datasets that are being used by a report control block or those that belong to the device type.

To edit a dataset, highlight its name, then select Edit. Make the desired changes, then select OK.

To delete a dataset, highlight its name. Select Delete, then select OK.