Prepare the Device to Be Recognized
The aim of this step is to configure the IP address assignment method of the device to be in accordance with that configured for the network planning.
This can be done during:
othe commissioning phase.
Depending on the device, different tools can be used:
oScrewdriver: for devices with rotary switch, dip switch, …(example: OTB)
oKeypad (example: ATV)
oPC, for devices that have to be configured with:
oEcoStruxure Machine Expert
oThird-party software
oIts Web server (example: OsiSense XGCS)
Depending on the IP address assignment, different actions can be done:
oDHCP: configure the DHCP device name in the device.
oBOOTP: refer to Device Configured in BOOTP.
oFixed IP: configure the IP address in the device.
If using EtherNet/IP, and using Electronic Keying, verify whether it is correctly configured.
Main Device Configuration Method
|
Tool |
IP address assignment method |
Description |
|---|---|---|
|
None |
DHCP |
The device is pre-configured in DHCP with the correct DHCP device name |
|
Screwdriver |
DHCP |
Use a screwdriver on the device (rotary switch, dip switch, …) to configure the DHCP device name. Example: Advantys OTB. |
|
BOOTP |
Use a screwdriver on the device (rotary switch, dip switch, …) in BOOTP. Example: XPSMCM. |
|
|
Fixed IP |
Use a screwdriver on the device (rotary switch, dip switch, …) to configure the IP address. |
|
|
Keypad |
DHCP |
Use the keypad of the device to configure DHCP device name. Example: ATV32. |
|
BOOTP |
Use the keypad of the device to configure the device in BOOTP. |
|
|
Fixed IP |
Use the keypad of the device to configure IP address. |
|
|
PC, tablet, … |
DHCP BOOTP Fixed IP |
Use PC or tablet to connect to the Device Web server and configure the network settings. Choose a connection method: oConnect the PC to an Ethernet port of the device The current IP address of the device must be known. oConnect a WIFER TCSEGWB13FA0 to an Ethernet port of the device. Connect the PC to the WIFER. |
|
PC |
DHCP BOOTP Fixed IP |
Use EcoStruxure Machine Expert (via DTM) to configure the network settings. Connect the PC to a dedicated communication port of the device. Example: Modbus serial line port of ATV32. For details, refer to Using DTMs to Configure Devices on Modbus Serial Line. |
|
DHCP BOOTP Fixed IP |
Use third-party software to configure the network settings. Choose a connection method: oConnect the PC to an Ethernet port of the device The current IP address of the device must be known. oConnect the PC to a dedicated communication port of the device. |
|
|
You may have to perform a device power cycle for parameter modifications to take affect. |
||
If the device IP address assignment is BOOTP, you must use EcoStruxure Machine Expert:
oSet the MAC address of the new device,
oLoad the new application in the controller.