Symptom |
Possible cause |
Resolution |
---|---|---|
Industrial Ethernet manager or Modbus TCP IOScanner is presented with a red triangle in the Devices tree. |
The configuration is not compliant with the controller version. |
oBuild > Clean all oBuild > Rebuild all oEnsure that the controller has the latest firmware version. |
A device is presented with a red triangle in the Devices tree. |
The controller is unable to communicate with the device. |
oVerify device wiring and powering. oVerify device IP address (by using the Remote ping service on the IP address of the device.). oVerify whether the device supports the read/write request. oVerify whether the accessed registers are relevant for this device. oVerify whether the accessed registers are not write-protected. oVerify that the FDR (Fast Device Replacement) service is properly configured inside the device. oVerify that the Master IP address parameter is properly configured inside the device. |
A device/channel is temporarily presented in red. |
The wiring is unstable. |
Verify the wiring. |
Configuration requires adjustment. |
oIncrease the health timeout value. oIncrease the repetition rate value. |
|
The load is too important for the protocol manager. |
Verify the Scanner Resources tab. |
|
Some states of the device are not presented in the application. |
For Modbus TCP slave device: The repetition rate is too slow (the value is too high). |
Decrease the repetition rate value for the channels associated to this device. |
Some states of the device are not presented in the application. |
The bus cycle task is not fast enough. |
oAssociate the scanner to a different task (Modbus TCP IOScanner). oDecrease the cycle value of the associated task. |