1 CompactFlash card slot
2 Battery compartment
The CompactFlash card slot is located on the operating cover of the controller.
The CompactFlash card slot is the receptacle for the permanent data storage (CF card) of the controller.
How to Replace the CompactFlash Card in Case of Servicing
Step |
Action |
---|---|
1 |
Set main switch to OFF position, or otherwise disconnect all power to the system. |
2 |
Prevent main switch from being switched back on. |
3 |
Hold the CompactFlash card with your thumb and forefinger and pull it out of the slot. |
4 |
To insert, carefully place the CompactFlash card on the guide rail and push it into the device. |
5 |
Push lightly until the CompactFlash card clicks in. |