Replacement of the Optional Module
Required Tool for Replacing the Optional Module
Module part |
Tool |
---|---|
Module shaft |
Cross slot maximum PH1 |
How to Disassemble the Optional Module
Step |
Action |
---|---|
1 |
Set main switch to OFF position, or otherwise disconnect all power to the system. |
2 |
Prevent main switch from being switched back on. |
3 |
Undo the two M3x6 screws on the module shaft. |
4 |
Withdraw the module from the cartridge. Result: The module is deinstalled now and the module shaft is empty. |
NOTICE |
INOPERABLE EQUIPMENT |
Do not remove the optional module when the controller is under power. |
Failure to follow these instructions can result in equipment damage. |
How to Install the Optional Module
The module is ready-to-use when delivered.
Step |
Action |
---|---|
1 |
Set main switch to OFF position, or otherwise disconnect all power to the system. |
2 |
Prevent main switch from being switched back on. |
3 |
Insert module into open slot. |
4 |
Screw module to module shaft with two M3x6 screws (tightening torque: 0.5 Nm (4.42 lbf in)). Result: The module is now installed. |
NOTICE |
INCORRECT INSERTION OF OPTIONAL MODULE |
Do not insert the optional module when the controller is under power. |
Failure to follow these instructions can result in equipment damage. |