Mechanical and Electrical Data
Technical Data PacDrive LMC Pro/Pro2
Category |
Parameter |
Value |
|||
---|---|---|---|---|---|
Product configuration |
Type code |
PacDrive LMC300 |
PacDrive LMC400 |
PacDrive LMC600 |
PacDrive LMC402 PacDrive LMC802 |
Configuration |
Processor |
up to Rev. 01: CPU Intel Celeron M 600 MHz 512 KB L2 cache |
CPU Intel Celeron M 1.5 GHz 1 MB L2 cache |
CPU Intel Pentium M 2.0 GHz 2 MB L2 cache |
CPU Intel Celeron 2000E 2.2 GHz 2 MB Smart Cache |
as of Rev. 02: CPU Intel Celeron M 1.5 GHz 1 MB L2 cache |
|||||
Memory |
512 MB DDR2 |
1 GB DDR3L |
|||
NV RAM |
128 KB |
128 KB |
256 KB |
||
Battery on the front for BIOS cmos, NVRAM and RTC |
Yes (battery maintenance interval: typically 5 years) |
||||
CompactFlash card |
At least 128 MB (accessible from the outside) |
||||
On/Off button |
Yes |
||||
Reset button |
Yes |
||||
Cooling |
Fan (temperature-controlled) |
||||
Real Time Clock (RTC) |
Yes |
||||
Diagnostics |
Watchdog |
Yes (maximum 2 A, maximum 60 Vdc) |
|||
Alphanumeric diagnostic display |
4 x 20 letters |
||||
Status LED indicators |
3 |
||||
Integrated data logger for diagnostic messages |
Yes |
||||
Integrated trace recorder (software oscilloscope) |
Yes |
||||
Remote maintenance |
Yes |
||||
Bus connections |
Integrated motion and field buses |
Sercos |
|||
Integrated additional fieldbus connection (configuration 1) |
PROFIBUS DP (master/slave) and |
||||
CAN (2.0B) |
|||||
Integrated additional fieldbus connection (configuration 2) |
RT-Ethernet (2 ports) and |
||||
PROFIBUS DP (master/slave) or 1 x CAN (2.0B) |
|||||
PacNet interface |
1 |
||||
Communication / interfaces |
Serial interfaces |
COM1: RS-232 |
|||
COM2: RS-422 / RS-485 |
|||||
Network connection |
1 x Ethernet 10/100 Base-T (auto negotiation, auto-MDI) |
1 x Ethernet 10/100/1000 Base-T (auto negotiation, auto-MDI) |
|||
USB connection |
1 x USB-2.0 (host for storage medium) |
||||
Master encoder interface |
1 Hiperface master encoder or |
||||
1 Incremental master encoder |
|||||
Programming interface |
Ethernet |
||||
Additional encoder input via PacNet interface with added BT-4/ENC module |
Hiperface master encoder or |
||||
Incremental master encoders |
|||||
Master encoder output via PacNet interface |
Incremental |
||||
Integrated OPC interface |
Yes |
||||
Diagnostic interface for remote maintenance |
Ethernet or modem |
||||
Communication protocols |
Http |
||||
Ftp |
|||||
ICMP (Ping) |
|||||
Optional slots for OM-C/OM-P/OM-NE |
2 |
||||
Programming- languages IEC 61131-3 |
– |
Continuous function chart (CFC) |
|||
Function block diagram (FBD) |
|||||
Instruction list (IL) |
|||||
Structured text (ST) |
|||||
Ladder diagram (LD) |
|||||
Sequential function chart (SFC) |
|||||
Touchprobe inputs |
Number |
16 (IEC 61131-2) |
|||
Range UIN 0 voltage |
0...6 Vdc |
||||
Range UIN 1 voltage |
20...33 Vdc |
||||
Input current |
IIN = 5 mA at UIN = 24 V |
||||
Polarized |
Yes |
||||
Input filter TP0...TP15 |
100 µs resolution |
||||
TP0 to TP15 |
10 µs at a Sercos cycle time of 1, 2, 4 ms |
||||
Additional inputs or Touchprobe inputs via PacNet |
Number |
maximum 64 |
|||
Fast PacNet inputs |
Number |
64 |
|||
Digital inputs |
Number |
20 (IEC 61131-2) |
|||
Range UIN 0 voltage |
0...6 Vdc |
||||
Range UIN 1 voltage |
20...33 Vdc |
||||
Input current |
IIN = 5 mA at UIN = 24 V |
||||
Polarized |
Yes |
||||
Input filter |
1 ms or 5 ms can be parameterized |
||||
Fast inputs (interrupt) |
Number |
4 (IEC 61131-2) |
|||
Range UIN 0 voltage |
0...6 Vdc |
||||
Range UIN 1 voltage |
20...33 Vdc |
||||
Input current |
IIN = 5 mA at UIN = 24 V |
||||
Polarized |
Yes |
||||
Input filter |
0.1 ms or 1 ms can be parameterized |
||||
Analog inputs |
Number |
2 |
|||
Range UIN |
-10...10 V |
||||
Resolution 12 bit (5 mV) |
|||||
Resistor 100 kOhm |
|||||
Range IIN |
-20...20 mA |
||||
Resolution 12 bit (5 µA) |
|||||
Resistor 500 Ohm |
|||||
Fast PacNet outputs |
Number |
64 |
|||
Digital outputs |
Number |
16 (IEC 61131-2) |
|||
Output voltage |
(+UL-3 V) < UOUT < +UL |
||||
Rated current |
Ie = 250 mA per output |
||||
Inrush current |
Iemax < 2 A for 1 s |
||||
Leakage current with 0 signal |
< 0.4 mA |
||||
Transmission time |
100 µs |
||||
Short circuit protection |
Yes |
||||
Analog outputs |
Number |
2 |
|||
Range UOUT |
-10...10 V |
||||
Resolution |
12 bit (5 mV) |
||||
Load |
> 5 kOhm (maximum offset < +/- 75 mV) |
||||
Power |
Maximum number of drives |
8 servo axes |
16 servo axes |
99 servo axes |
16 servo axes (PacDrive LMC402) 130 servo axes (PacDrive LMC802) |
Power supply |
Power supply unit |
without UPS (with UPS) |
|||
oup to Rev. 01: 1.5 A (2.5 A) oas of Rev. 02: 2.0 A (3 A) |
2.0 A (3 A) |
2.0 A (3 A) |
2.0 A (3 A) |
||
Supply voltage |
DC +24 V -15 %/+25 % |
||||
Inrush current |
maximum 20 A / 1 ms |
||||
Voltage drop immunity |
Up to 25 ms. |
||||
UPS |
Yes (optional) |
|
|||
Power consumption of power supply |
oup to Rev. 01: 24 W (66 W) oas of Rev. 02: 48 W (72 W) |
48 W (72 W) |
48 W (72 W) |
48 W (72 W) |
|
Dimensions |
Dimensions of housing |
DxWxH: 243 x 100 x 310 mm / 9.57 x 3.94 x 12.20 in |
|||
Weight |
Weight (with packaging) |
3.5 kg (4.1 kg) / 7.71 lb (9.03 lb) |
|||
Pollution degree |
2 (according to CN 60664-1) |