Issue: Message Server is busy is Displayed
After you have started the OPC client and you attempt to establish a connection to the OPC server, the operating system message Server is busy is displayed.
When starting the OPC server, a connection to the controller cannot be established immediately. In this case, the OPC server waits until the waiting time has elapsed. It then retries to connect to the client.
Reduce the value of the Wait time (s) parameter in the controller configuration of the OPC configuration tool.
The virtual RAM of the computer running the visualization is not sufficient.
Increase the virtual RAM of the computer running the visualization.