Issue: Items Are Not Available in the OPC Client
Not all items are provided in the OPC client (OPC state OPC_RUNNING).
The symbol file is not correct.
The symbol file has not been generated when the new project has been uploaded to the controller. Thus, the OPC server is still processing the old symbol file.
Regenerate the symbol file by modifying the Logic Builder / EPAS-4 settings and download the project to the controller. Also refer to symbol file configuration.
The project name has been changed but the OPCServer.ini file has not been adapted. This cause is only available in simulation mode.
Adapt the settings via the OPC configuration tool.
The items have been changed in the project, but they have not been added to or modified in the symbol configuration or symbol file.
In Logic Builder / EPAS-4, verify the symbol configuration. Modified variable names are not automatically deleted. You must remove and reinsert them manually.
New or modified items are not displayed, although the symbol configuration/symbol file has been transferred correctly.
The OPC server is running as a service.
Step |
Action |
---|---|
1 |
Close the OPC client and the service for the OPC client. |
2 |
Restart the service. |
3 |
Restart the client. |
One or several controllers have been disabled in multi-controller operation.
Verify the configuration of the OPC server and enable the controllers.
The project in the controller has not been downloaded with Logic Builder via the gateway server/Gateway Management Console used by the OPC server. Thus, the OPC server is still processing the old symbol file.
Two solutions are available for EPAS-4/Logic Builder:
oDownload the project with Logic Builder to the controller via the gateway server/Gateway Management Console of the OPC server.
oCopy the symbol file from the EPAS-4/Logic Builder computer, and paste it on the computer running the gateway server/Gateway Management Console of the OPC server.