8509 Sercos slave SW not supported
Refer to Diagnostic class (standard): 3
The firmware version of the Sercos slave is incorrect.
|
Cause |
Solution |
|---|---|
|
The firmware version of the Sercos slaves is greater than the firmware version of the PacDrive controller in the first four positions. |
Update the controller version. |
|
Ext. diagnosis = Vxx.yy.zz BLD The Sercos slave is in bootloader mode. The version of the Bootloader is shown in the message logger under Ext. Diagnosis. The Sercos slave can also be found using the information on the object and instance provided in the message logger. |
oReduce the number of objects with real-time tasks (for example, virtual axes, virtual encoders, logical encoders, sum encoders, ...). oReset the Sercos slaves. oAcknowledge the diagnostic message. The Sercos bus is running up in phase 4. |