8601 Master Encoder signal out of range

Description

Refer to Diagnostic class (standard): 3

Unable to receive analog data from the SinCos master encoder.

NOTE: Hardware encoder error. Reset the PacDrive controller. Acknowledge the diagnostic message only after reinitialization or homing of the system has been acknowledged by the program. If necessary, use the functions FC_SysReset() or FC_PrgResetAndStart().

Cause

Solution

Detected wiring error: The encoder cable is not plugged in correctly or is inoperable.

Verify the encoder cable and replace if necessary.

Detected hardware error: The SinCos encoder is inoperable.

Replace the encoder.

Detected hardware error: The PacDrive LMC is inoperable.

Replace the controller.