8733 Fatal bus error

Description

Refer to Diagnostic class (standard): 3

Further bus communication is not possible due to a detected bus error.

NOTE: No data exchange with bus terminal BT-4 ENC1. Position loss of the master encoder connected to bus terminal BT-4/ENC1. Acknowledge the diagnostic message only after reinitial­ization or homing of the system has been acknowledged by the program. If necessary, use the function FC_SysReset() or FC_PrgResetAndStart().

Cause

Solution

Detected wiring error: Incorrect bus topology.

Verify and correct or replace if necessary the terminals, transmission lines, and so on.

EMC errors found.

Verify and correct or replace if necessary the wiring and EMC protection.

Ext. diagnosis

Meaning

asynchronous

A synchronization error is detected. The touchprobes on the BT-4/DIO1 are not working.

Verify the jumper cable that connects the controller to the optional module PN-4 (in the controller).

clock miss

A communication error is detected in PacNet.

This may be due to various causes:

oPacNet loop not closed

oPacNet terminating plug is missing

oA module connected to PacNet is inoperable (for example, no power)

Verify the PacNet loop and the modules in the loop.

Cause

Solution

Sercos cycle time 4 ms and PacDrive LMC-FPGA version < V0x02 (x = Hardware-ID, for example Id=2 -> FPGA version = V0202)

Update PacDrive LMC-FPGA version to at least version V0x02