8990 Firmware update not possible
Refer to Diagnostic class (standard): 1
The firmware of the device could not be updated.
|
Cause |
Solution |
|---|---|
|
Sercos is in phase 4. A firmware update is only possible in phase 0. |
Switch Sercos to phase 0. |
|
The selected firmware is not compatible with the device (for example, the Lexium 52 firmware shall be installed in a Lexium 62 drive). |
Verify whether the selected firmware is compatible with the device. |