Refer to Diagnostic class (standard): 3
DiagExtMsg: ModuleNbr.x
x = number of the module under the Sercos III bus interface (TM5NS31)
|
If... |
Then... |
|---|---|
|
The module is used with one of the following configuration profiles: oTM5SDM8DTS_TSITSO oTM5SDM8DTS_OITSO oTM5SDM8DTS_HFOIDO oTM5SDM8DTS_DIHFOO |
This diagnostic message is triggered by the TM5SDM8DTS module during Sercos phase change to phase 2.
|
|
The value of the TM5CycleTime parameter (parameter of the Sercos III bus interface TM5NS31) is less than 500 µs. |
The Sercos phase up is stopped and the diagnostic message is triggered.
For example, the following configuration triggers the diagnostic message 8065 TM5 cycle time not valid with DiagExtMsg: ModuleNbr.2 as the TM5SDM8DTS_HFOIDO does not work with the configured TM5CycleTime.
oSercos III bus interface (TM5NS31) with TM5CycleTime = 250 µs
oTM5SPS3
oTM5SDM8DTS_HFOIDO