General

Description

4 DI; 4 DI; 4 DI; 4 DO; 4 DO

Compact I/O module 24 Vdc with 3x4 digital inputs and 2x4 digital outputs

The module consists of the following five submodules:

oThree submodules with four digital inputs

oTwo submodules with four digital outputs

Configuration Register

Register

Meaning

Default

Data type

Submodule 1

0+0

Digital inputs 1–4

USINT

0+18

Digital input filter

10

USINT

Submodule 2

32+0

Digital inputs 1–4

USINT

32+18

Digital input filter

10

USINT

Submodule 3

64+0

Digital inputs 1–4

USINT

64+18

Digital input filter

10

USINT

Submodule 4

96+0

Digital outputs 1–4

INT

96+20

Delay time error (μs)

ULONG

96+24

Triggering time error (μs)

ULONG

96+30

Status of digital outputs 1–4

USINT

Submodule 5

128+0

Digital outputs 1–4

INT

128+20

Delay time error (μs)

ULONG

128+24

Triggering time error (μs)

ULONG

128+30

Status of digital outputs 1-4

USINT

For further information, see the TM5 compact I/O modules hardware manual.