ErrorDeceleration

General

Type

EF

Offline editable

Yes

Devices supporting the parameter

SinCos encoder input,

Incremental Encoder Input,

Encoder network (Synchronization encoder output),

C2C Encoder input

Traceable

Yes

Functional Description

A synchronization error on coupled machines is detected in the following cases:

o8601 "Master Encoder signal out of range" (SinCos)

o8782 "Master Encoder signal out of range" (incremental encoder input )

o8522 C2C encoder error detected (C2C Encoder input)

The parameter ErrorDeceleration can bring the system to a standstill with a defined velocity deceleration. When a track error is detected, the velocity is set to 0 with the defined deceleration.

If 0 is entered in ErrorDeceleration, then no velocity deceleration is created by the system.

Encoder behavior when ErrorDeceleration = 0 and track error has been detected:

oSinCos encoder input (physical master encoder): The velocity remains constant.

oIncremental Encoder Input: The velocity always follows the received incremental encoder input signals. If the connection to the encoder is interrupted, the velocity is lowered to 0.

oSynchronization encoder output (Encoder network): The last known velocity is maintained.

oC2C Encoder input: The last known velocity is maintained.