Create the Second Reference Point

Conditions

The following conditions must be respected:

oModule_Ref must have a correct value

oCycle_number must have a correct value

oReference 1 must be previously established

Procedure

The procedure sets the Raw_Ref2 field of the s_strainGaugeParameter structure.

Step

Action

1

Create and stabilize the conditions that are representative of the measurement required for the second reference point.

2

Set the inputs of the StrainGauge function block to following values:

Tare_Enable = 0

Ref1_Enable = 0

Ref2_Enable = 1

3

Set the function block input xExecute to 1.

4

When xDone = 1, s_strainGaugeParameter.RawRef2 is set to the average value calculated by the function block.

5

Set the corresponding calibrated value you wish to associate with Raw_Ref2 in the s_strainGaugeParameter.Calibrate_Ref2.

Defining both reference points allows to establish the calibration line:

G-SE-0017998.1.gif-high.gif