SystemVoltageBasic - Functional Description

Overview

Type:

Function block

Available as of:

V1.0.0.0

G-SE-0075852.1.png

 

 

Functional Description

The function block SystemVoltageBasic returns and resets the voltage registers of the system avatar.

Interface

Input

Data type

Description

iq_TeSysIslandRef

FB_TeSys_island

Reference to the TeSys island device.

i_xExecute

BOOL

Upon a rising edge of this input, the function block starts the execution. The outputs q_xDone, q_xError, q_etResult, and q_etResultMsg are reset with the falling edge of i_xExecute. Refer to Behavior of Function Blocks with the Input i_xExecute.

i_xResetMaxVRMS

BOOL

If this input is set to TRUE, the value of the parameter q_udiResetMaxVRMS is reset.

i_xResetMaxUnbalanceVltg

BOOL

If this input is set to TRUE, the value of the parameter q_udiResetMaxUnbalanceVltg is reset.

i_xResetVltgFlctnStatus

BOOL

If this input is set to TRUE, the value of the parameter q_udiResetVltgFlctnStatus is reset.

Output

Data type

Description

q_xError

BOOL

If this output is set to TRUE, an error has been detected. For details, refer to q_etResult and q_etResultMsg.

q_etResult

ET_Result

Provides diagnostic and status information as a numeric value.

q_sResultMsg 

STRING[30]

Provides additional diagnostic and status information as a text message.

q_xBusy

BOOL

If this output is set to TRUE, the function block execution is in progress.

q_xDone

BOOL

If this output is set to TRUE, the execution has been completed successfully.

q_xUpstreamVltgFlctnStatus

BOOL

If this output is set to TRUE, a voltage dip or swell is detected. Can be reset with i_xResetVltgFlctnStatus.

q_uiAvgVRMS

UINT

Average IRMS voltage on three phases (Unit: mV).

q_uiMaxAvgVRMS

UINT

Maximum voltage the system measured (Unit: mV).

q_stMaxAvgVRMSTimestamp

SysTimeRtc.RTS_SYSTIMEDATE

Date and time when maximum average voltage value was recorded.

Refer to the SysTimeRtc library.

q_uiVRMSPhase1

UINT

Average IRMS voltage between L1 and neutral.

(Unit: V)

q_uiVRMSPhase2

UINT

Average IRMS voltage between L2 and neutral.

(Unit: V)

q_uiVRMSPhase3

UINT

Average IRMS voltage between L3 and neutral.

(Unit: V)

q_usiUnbalancedVltg

USINT

Unbalance voltage in percent (%).

q_usiMaxUnbalancedVltg

USINT

Maximum unbalance voltage in percent (%).

q_stMaxUnbalancedVltgTimestamp

SysTimeRtc.RTS_SYSTIMEDATE

Date and time of maximum unbalance voltage.

Refer to the SysTimeRtc library.

q_xPhaseSequence

BOOL

If this output is set to TRUE, the phase order is ACB (FALSE = phase order ABC).

q_usiFrequency

USINT

Main power voltage frequency (line frequency as measured on phase 1).

(Unit: Hertz)