NOTE:
oBox Module environmental specifications follow those of the connected Display Module.
oWhen using any of the options for this product, check the specifications for special conditions or cautions that may apply to this product.
Specification |
HMIDT35X |
HMIDT65X |
HMIDT75X |
---|---|---|---|
Physical environment |
|||
Ambient air temperature*1 |
-30...65 °C (-22...149 °F) (T4) When installing and wiring: -5...65 °C (23...149 °F) |
-30...70 °C (-22...158 °F) (T4) When installing and wiring: -5...70 °C (23...158 °F) |
-20...60 °C (-4...140 °F) (T4) When installing and wiring: -5...60 °C (23...140 °F) |
Storage temperature*1 |
-30...70 °C (-22...158 °F) |
-30...70 °C (-22...158 °F) |
-20...60 °C (-4...140 °F) |
Ambient air and storage humidity |
10%...90% RH (Non condensing, wet bulb temperature 39 °C [102.2 °F] or less) |
||
Dust |
0.1 mg/m3 (10-7 oz/ft3) or less (free of conductive dust particles on all surfaces other than the front face) |
||
Pollution degree |
3 for front face, 2 for other sides. |
||
Corrosive gases |
Free of corrosive gases |
||
Atmospheric pressure (operating altitude) |
800...1,114 hPa (2,000 m [6,561 ft] or lower) |
||
UV resistance (front side) |
Cutoff: 99% or more (380 nm) |
||
Mechanical environment |
|||
Vibration resistance*1 |
IEC 60068-2-6 compliant 5...9 Hz Single amplitude 7 mm (0.28 in) 9...150 Hz Fixed acceleration: 19.6 m/s2 X, Y, Z directions for 10 cycles (approximately 100 minutes) IEC 61373: 1999 (Category 1, Class B) 5≤f≤150 Hz (weight < 500 kg: f1=5 Hz, f2=150 Hz) acceleration: Up and down: 7.90 m/s2, Right and left: 3.50 m/s2, Back and forward: 5.50 m/s2 |
IEC 60068-2-6 compliant 5...9 Hz Single amplitude 3.5 mm (0.14 in) 9...150 Hz Fixed acceleration: 9.8 m/s2 X, Y, Z directions for 10 cycles (approximately 100 minutes) IEC 61373: 1999 (Category 1, Class B) 5≤f≤150 Hz (weight < 500 kg: f1=5 Hz, f2=150 Hz) acceleration: Up and down: 7.90 m/s2, Right and left: 3.50 m/s2, Back and forward: 5.50 m/s2 |
|
Shock resistance*1 |
IEC 60068-2-27 compliant 392 m/s2, 11 ms, X, Y, Z directions for 3 times |
IEC 60068-2-27 compliant 147 m/s2, X, Y, Z directions for 3 times |
|
Electrical environment |
|||
Electronic fast transient/burst immunity |
IEC 61000-4-4 2 kV: Power port 1 kV: Signal ports |
||
Electrostatic discharge immunity |
Contact discharge method: 6 kV Air discharge method: 8 kV (IEC/EN 61000-4-2 Level 3) |
*1 When using a Fieldbus unit, use this product within the specifications of the Fieldbus unit.
Do not operate or store the panel where chemicals evaporate, or where chemicals are present in the air:
oCorrosive chemicals: Acids, alkalines, liquids containing salt.
oFlammable chemicals: Organic solvents.
|
INOPERATIVE EQUIPMENT |
Do not allow water, liquids, metal, and wiring fragments to enter the panel case. |
Failure to follow these instructions can result in injury or equipment damage. |