TM5 Power Distribution Mounting Rules

PDMs Mounting Rules

Installing a PDM according to these rules automatically establishes a new 24 Vdc I/O power segment for I/O expansions to the right of the PDM.

The TM5SPS2• PDM can be placed at the end of the configuration. In this case, it supplies only the TM5 power bus.

Rules:

oDo not mount PDMs side by side

oDo not mount a PDM and a Transmitter or Receiver module side by side

oDo not mount a PDM and an Interface Power Distribution Module (IPDM) side by side

oDo not mount a PDM next to any of the following modules: TM5SAI2H, TM5SAI4H, TM5SAO4L or TM5SAO4H

EcoStruxure Machine Expert software is designed to help prevent the installation of incompatible modules side by side.

Warning_Color.gifWARNING

UNINTENDED EQUIPMENT OPERATION

Do not mount a Power Distribution Module (PDM) next to any one of the following modules:

oPower Distribution Module (PDM)

oTransmitter module TM5SBET1 or TM5SBET7

oReceiver module TM5SBER2

oInterface Power Distribution Module TM5SPS3 (IPDM)

oAnalog input module TM5SAI2H or TM5SAI4H

oAnalog output module TM5SAO4L or TM5SAO4H

Failure to follow these instructions can result in death, serious injury, or equipment damage.

IPDM Mounting Rules

Rules:

oDo not mount a PDM next to an IPDM

oDo not mount a Transmitter or Receiver module next to an IPDM

oDo not mount any of the following modules: TM5SAI2H, TM5SAI4H, TM5SAO4L or TM5SAO4H next to an IPDM

Performance Distributed I/O Configuration software is designed to help prevent the installation of incompatible modules side by side.

Warning_Color.gifWARNING

UNINTENDED EQUIPMENT OPERATION

Do not mount any one of the following modules next to an Interface Power Distribution Module (IPDM):

oPower Distribution Module (PDM)

oTransmitter module TM5SBET1 or TM5SBET7

oReceiver module TM5SBER2

oAnalog input module TM5SAI2H or TM5SAI4H

oAnalog output module TM5SAO4L or TM5SAO4H

Failure to follow these instructions can result in death, serious injury, or equipment damage.