Current Supplied and Consumption Tables on the 24 Vdc I/O Power Segment

Introduction

The following tables give a synthesis of the current supplied and current consumed on the 24 Vdc I/O power segment by the TM7 System blocks.

NOTE: There is no current supplied or consumed by the TM7 Power Distribution Block (PDB) on the 24 Vdc I/O power segment.

TM7 System Blocks

The following table gives the current supplied and consumed by the TM7 System blocks on the 24 Vdc I/O power segment:

Reference

On the 24 Vdc I/O Power Segment

Maximum Current Supplied(1) (mA)

Current Consumed by the Electronic (mA)

Maximum Current Consumed by the Loads (mA)

Maximum Current Consumed by the Sensor/Actuator (mA)

Digital input

TM7BDI8B

8000

42

500

TM7BDI16B

8000

21

500

TM7BDI16A

8000

21

500

Digital output

TM7BDO8TAB

8000

84

8000

500

Digital mixed input/output

TM7BDM8B

8000

105

4000

500

TM7BDM16A

8000

125

8000

500

TM7BDM16B

8000

125

8000

500

Analog input

TM7BAI4VLA

8000

125

500

TM7BAI4CLA

8000

125

500

TM7BAI4TLA

8000

63

TM7BAI4PLA

8000

108

Analog output

TM7BAO4VLA

8000

167

500

TM7BAO4CLA

8000

188

500

Analog mixed input/output

TM7BAM4VLA

8000

125

500

TM7BAM4CLA

8000

125

500

(1) When connecting the 24 Vdc I/O power IN connector to an external power supply