This section describes the configuration of the TM3 Ethernet bus coupler as an Ethernet/IP adapter.
For further information about Ethernet/IP, refer to the www.odva.org website.
Ethernet/IP Adapter Configuration
To configure your TM3 Ethernet bus coupler as an EtherNet/IP adapter, add the bus coupler to your project and select EtherNet IP Scanner > TM3BCEIP.
EtherNet/IP Parameters Configuration
To configure the Ethernet/IP parameters, double-click the bus coupler node in the Devices tree.
In the Target Settings tab, you can configure the following parameters:
|
Element |
Description |
|---|---|
|
Address Settings |
|
|
IP Address by DHCP |
IP address is obtained via DHCP. |
|
Device name used to retrieve IP address through DHCP, maximum 15 characters. |
|
|
IP Address by BOOTP |
MAC address of the bus coupler. |
|
Fixed IP Address |
IP address of the bus coupler. |
|
Electronic Keying |
|
|
Check Device Type |
Type of the bus coupler. |
|
Check Vendor Type |
Vendor code of the bus coupler. |
|
Check Product Type |
Product code of the bus coupler. |
|
Check Major Revision |
Firmware major version. |
|
Check Minor Revision |
Firmware minor version. |
|
Protocol on the fieldbus |
|
|
Protocol used by the device |
Protocol used. You cannot edit this field. |
Electronic Keying signatures are used to identify the bus coupler.
Electronic Keying is information contained in the firmware of the bus coupler (Vendor Code, Product Code, …).
When the controller scanner starts, it compares each selected electronic keying value with the corresponding information in the TM3 Ethernet bus coupler.
If the TM3 Ethernet bus coupler values are not the same as the application values, the controller no longer communicates with the TM3 Ethernet bus coupler.
Connections on Ethernet/IP Adapter
To access a target device, an Originator opens a connection which can include several sessions that send requests.
One explicit connection uses one session (a session is a TCP or UDP connection).
One I/O connection uses one session.
The following table shows the Ethernet/IP connections limitations:
|
Characteristic |
Maximum |
|---|---|
|
Explicit connections |
16 (Class 3) |
|
I/O connections |
1 (Class 1) Exclusive Owner 15 (Class 1) Listen Only |
|
Sessions |
16 |
NOTE: The TM3 bus coupler supports cyclic connections. If an Originator opens a connection using a change of state as a trigger, packets are sent at the RPI rate.
When the data exchanges are configured, you can map variables to be used by the program.
Defined variables are listed in the EtherNet/IP I/O Mapping tab.
For more information on this tab, refer to I/O Mapping Dialog.
Select the Bus cycle task to synchronize the EtherNet/IP adapter data:
oUse parent bus cycle setting (the default),
oMAST
oAny task of the application
NOTE: This parameter defines the task responsible for copying the %IW and %QW registers from/to the bus coupler.
The TM3 bus coupler supports the following objects:
|
Object class |
Class ID (hex) |
Effect on Interface Behavior |
|---|---|---|
|
TM3 bus coupler configuration object |
65 |
Stores TM2/TM3 module configurations. |
|
TM3 bus coupler feature configuration object |
64 |
Used to prepare/apply configuration. |
The controller supports the following objects:
|
Object class |
Class ID (hex) |
Cat. |
Number of Instances |
Effect on Interface Behavior |
|---|---|---|---|---|
|
01 |
1 |
1 |
Supports the reset service |
|
|
02 |
1 |
1 |
Explicit message connection |
|
|
04 |
2 |
2 |
Defines I/O data format |
|
|
06 |
|
1 |
– |
|
|
F5 |
1 |
1 |
TCP/IP configuration |
|
|
F6 |
1 |
1 |
Counter and status information |
|
|
350 |
1 |
1 |
– |
|
|
352 |
1 |
1 |
– |
|
|
353 |
1 |
1 |
– |
|
|
TM3 Bus Coupler Feature Configuration Object |
64 |
1 |
2 |
– |
Identity Object (Class ID = 01 hex)
The following table describes the class attributes of the Identity Object:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Value (hex) |
Details |
|---|---|---|---|---|---|
|
1 |
Get |
Revision |
UINT |
01 |
Implementation revision of the Identity Object |
|
2 |
Get |
Max Instances |
UINT |
01 |
The largest instance number |
|
3 |
Get |
Number of Instances |
UINT |
01 |
The number of object instances |
|
6 |
Get |
Max Class Attribute |
UINT |
07 |
The largest class attributes value |
|
7 |
Get |
Max Instance Attribute |
UINT |
07 |
The largest instance attributes value |
The following table describes the Class Services:
|
Service Code (hex) |
Name |
Description |
|---|---|---|
|
01 |
Get Attribute All |
Returns the value of all class attributes |
|
0E |
Get Attribute Single |
Returns the value of the specified attribute |
The following table describes the Instance Services:
|
Service Code (hex) |
Name |
Description |
|---|---|---|
|
01 |
Get Attribute All |
Returns the value of all class attributes |
|
05 |
Reset (1) |
Initializes EtherNet/IP component (controller reboot) |
|
0E |
Get Attribute Single |
Returns the value of the specified attribute |
(1) Reset Service description:
When the Identity Object receives a Reset request, it:
odetermines whether it can provide the type of reset requested
oresponds to the request
oattempts to perform the type of reset requested
The Reset common service has one specific parameter, Type of Reset (USINT), with the following values:
|
Value |
Type of Reset |
|---|---|
|
0 |
Reboots the controller NOTE: This is the default value if this parameter is omitted. |
|
1 |
Not supported |
|
2 |
Not supported |
|
3...99 |
Reserved |
|
100...199 |
Vendor specific |
|
200...255 |
Reserved |
The following table describes the Instance attributes:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Value (hex) |
Details |
|---|---|---|---|---|---|
|
1 |
Get |
Vendor ID |
UINT |
F3 |
Schneider Automation ID |
|
2 |
Get |
Device type |
UINT |
0C |
EIP Adapter |
|
3 |
Get |
Product code |
UINT |
1009 |
Bus coupler product code |
|
4 |
Get |
Revision |
Struct of USINT, USINT |
– |
Product revision number of the bus coupler (1). Equivalent to the 2 low bytes of the bus coupler version |
|
5 |
Get |
Status |
WORD |
– |
Status word(2) |
|
6 |
Get |
Serial number |
UDINT |
– |
Serial number of the bus coupler |
|
7 |
Get |
Product name |
Struct of USINT, STRING |
TM3BCEIP |
– |
(1) Mapped in a WORD:
oMSB: minor revision (second USINT)
oLSB: major revision (first USINT)
Example: 0205 hex means revision V5.2.
(2) Status word (Attribute 5):
|
Bit |
Name |
Description |
|---|---|---|
|
0 |
Owned |
TRUE indicates that the device is a owner. |
|
1 |
Reserved |
– |
|
2 |
Configured |
TRUE indicates that the device application has been configured. |
|
3 |
Reserved |
– |
|
4...7 |
Extended Device Status |
o0: Self-testing or undetermined o1: Firmware update in progress |
|
8 |
Minor Recoverable Fault |
TRUE indicates that the device detected an error, which, under most circumstances, is recoverable. This type of event does not lead to a change in the device state. |
|
9 |
Minor Unrecoverable Fault |
TRUE indicates that the device detected an error, which, under most circumstances, is unrecoverable. This type of event does not lead to a change in the device state. |
|
10 |
Major Recoverable Fault |
TRUE indicates the device detected an error, which requires the device to report an exception and enter into the HALT state. This type of event leads to a change in the device state, but, under most circumstances, is recoverable. |
|
11 |
Major Unrecoverable Fault |
TRUE indicates the device detected an error, which requires the device to report an exception and enter into the HALT state. This type of event leads to a change in the device state, but, under most circumstances, is not recoverable. |
|
12...15 |
Reserved |
– |
Message Router Object (Class ID = 02 hex)
The following table describes the class attributes of the Message Router object:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Value (hex) |
Details |
|---|---|---|---|---|---|
|
1 |
Get |
Revision |
UINT |
01 |
Implementation revision number of the Message Router Object |
|
2 |
Get |
Max Instances |
UINT |
01 |
The largest instance number |
|
3 |
Get |
Number of Instance |
UINT |
01 |
The number of object instances |
|
4 |
Get |
Optional Instance Attribute List |
Struct of UINT, UINT [ ] |
– |
The first 2 bytes contain the number of the optional instance attributes. Each following pair of bytes represents the number of other optional instance attributes (from 100 to 119). |
|
5 |
Get |
Optional Service List |
UINT |
0A |
The number and list of any implemented optional services attribute (0: no optional services implemented) |
|
6 |
Get |
Max Class Attribute |
UINT |
07 |
The largest class attributes value |
|
7 |
Get |
Max Instance Attribute |
UINT |
02 |
The largest instance attributes value |
The following table describes the Class Services:
|
Service Code (hex) |
Name |
Description |
|---|---|---|
|
01 |
Get_Attribute_All |
Returns the value of all class attributes |
|
0E |
Get_Attribute_Single |
Returns the value of the specified attribute |
The following table describes the Instance Services:
|
Service Code (hex) |
Name |
Description |
|---|---|---|
|
01 |
Get_Attribute_All |
Returns the value of all class attributes |
|
0E |
Get_Attribute_Single |
Returns the value of the specified attribute |
The following table describes the Instance attributes:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Value |
Description |
|---|---|---|---|---|---|
|
1 |
Get |
Implemented Object List |
Struct of UINT, UINT [ ] |
– |
Implemented Object list. The first 2 bytes contain the number of implemented objects. Each 2 bytes that follow represents another implemented class number. This list contains the following objects: oIdentity oMessage Router oAssembly oConnection Manager oQoS oPort oTCP/IP Interface oEthernet Link |
|
2 |
Get |
Number available |
UINT |
16 |
Maximum number of concurrent CIP (Class 1 or Class 3) connections supported |
Assembly Object (Class ID = 04 hex)
The following table describes the class attributes of the Assembly object:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Value (hex) |
Details |
|---|---|---|---|---|---|
|
1 |
Get |
Revision |
UINT |
02 |
Implementation revision of the Assembly Object |
|
2 |
Get |
Max Instances |
UINT |
65 |
The largest instance number |
|
3 |
Get |
Number of Instances |
UINT |
03 |
The number of object instances |
|
4 |
Get |
Optional Instance Attribute List |
Struct of: UINT UINT [ ] |
01 04 |
The first 2 bytes contain the number of optional instance attributes. Each following pair of bytes represents the number of other optional instance attributes. |
|
5 |
Get |
Optional Service List |
UINT |
Not supported |
The number and list of any implemented optional services attribute (0: no optional services implemented) |
|
6 |
Get |
Max Class Attribute |
UINT |
07 |
The largest class attributes value |
|
7 |
Get |
Max Instance Attribute |
UINT |
04 |
The largest instance attributes value |
The following table describes the Class Services:
|
Service Code (hex) |
Name |
Description |
|---|---|---|
|
0E |
Get Attribute Single |
Returns the value of the specified attribute |
The following table describes the Instance Services:
|
Service Code (hex) |
Name |
Description |
|---|---|---|
|
0E |
Get Attribute Single |
Returns the value of the specified attribute |
|
10 |
Set Attribute Single |
Modifies the value of the specified attribute |
Instances Supported
The bus coupler supports 2 Assemblies:
|
Name |
Instance |
Data Size |
|---|---|---|
|
TM3BC IO Modules Output Data |
100 |
2...64 words |
|
TM3BC IO Modules Input Data |
101 |
2...64 words |
Assembly assignment
The following table describes the Instance attributes:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Value |
Description |
|---|---|---|---|---|---|
|
3 |
Get/Set |
Instance Data |
ARRAY of Byte |
– |
Data Set service only available for the controller output |
|
4 |
Get |
Instance Data Size |
UINT |
128 |
Size of data in byte |
Connection Manager Object (Class ID = 06 hex)
The following table describes the class attributes of the Assembly Object:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Value (hex) |
Details |
|---|---|---|---|---|---|
|
1 |
Get |
Revision |
UINT |
01 |
Implementation revision of the Connection Manager Object |
|
2 |
Get |
Max Instances |
UINT |
01 |
The largest instance number |
|
3 |
Get |
Number of Instances |
UINT |
01 |
The number of object instances |
|
4 |
Get |
Optional Instance Attribute List |
Struct of: UINT UINT [ ] |
– |
The number and list of the optional attributes. The first word contains the number of attributes to follow and each following word contains another attribute code. Following optional attributes include: ototal number of incoming connection open requests othe number of requests rejected due to non-conforming format of the Forward Open othe number of requests rejected because of insufficient resources othe number of requests rejected due to parameter value sent with the Forward Open othe number of Forward Close requests received othe number of Forward Close requests with an invalid format othe number of Forward Close requests that could not be matched to an active connection othe number of connections that have timed out because the other side has stopped producing, or a network was disconnected |
|
6 |
Get |
Max Class Attribute |
UINT |
07 |
The largest class attributes value |
|
7 |
Get |
Max Instance Attribute |
UINT |
08 |
The largest instance attributes value |
The following table describes the Class Services:
|
Service Code (hex) |
Name |
Description |
|---|---|---|
|
01 |
Get Attribute All |
Returns the value of all class attributes |
|
0E |
Get Attribute Single |
Returns the value of the specified attribute |
The following table describes the Instance Services:
|
Service Code (hex) |
Name |
Description |
|---|---|---|
|
01 |
Get Attribute All |
Returns the value of all instance attributes |
|
0E |
Get Attribute Single |
Returns the value of the specified attribute |
|
4E |
Forward Close |
Closes an existing connection |
|
52 |
Unconnected Send |
Sends a multi-hop unconnected request |
|
54 |
Forward Open |
Opens a new connection |
The following table describes the Instance attributes:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Value |
Description |
|---|---|---|---|---|---|
|
1 |
Get |
Open Requests |
UINT |
– |
Number of Forward Open service requests received |
|
2 |
Get |
Open Format Rejects |
UINT |
– |
Number of Forward Open service requests which were rejected due to invalid format |
|
3 |
Get |
Open Resource Rejects |
ARRAY of Byte |
– |
Number of Forward Open service requests which were rejected due to lack of resources |
|
4 |
Get |
Open Other Rejects |
UINT |
– |
Number of Forward Open service requests which were rejected for reasons other than invalid format or lack of resources |
|
5 |
Get |
Close Requests |
UINT |
– |
Number of Forward Close service requests received |
|
6 |
Get |
Close Format Requests |
UINT |
– |
Number of Forward Close service requests which were rejected due to invalid format |
|
7 |
Get |
Close Other Requests |
UINT |
– |
Number of Forward Close service requests which were rejected for reasons other than invalid format |
|
8 |
Get |
Connection Timeouts |
UINT |
– |
Total number of connection timeouts that have occurred in connections controlled by this Connection Manager |
TCP/IP Interface Object (Class ID = F5 hex)
This object maintains link specific counters and status information for an Ethernet 802.3 communication interface.
The following table describes the class attributes of the TCP/IP Interface Object:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Value |
Details |
|---|---|---|---|---|---|
|
1 |
Get |
Revision |
UINT |
4 |
Implementation revision of the TCP/IP Interface Object |
|
2 |
Get |
Max Instances |
UINT |
1 |
The largest instance number |
|
3 |
Get |
Number of Instances |
UINT |
1 |
The number of object instances |
|
4 |
Get |
Optional |
Struct of: UINT UINT [ ] |
– |
The first 2 bytes contain the number of optional instance attributes. Each following pair of bytes represents the number of other optional instance attributes. |
The following table describes the Class Services:
|
Service Code (hex) |
Name |
Description |
|---|---|---|
|
01 |
Get Attribute All |
Returns the value of all class attributes |
|
0E |
Get Attribute Single |
Returns the value of the specified attribute |
Instance Codes
Only instance 1 is supported.
The following table describes the Instance Services:
|
Service Code (hex) |
Name |
Description |
|---|---|---|
|
01 |
Get Attribute All |
Returns the value of all instance attributes |
|
0E |
Get Attribute Single |
Returns the value of the specified instance attribute |
The following table describes the Instance Attributes:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Value |
Description |
|---|---|---|---|---|---|
|
1 |
Get |
Status |
DWORD |
Bit level |
o0: The interface configuration attribute has not been configured. o1: The interface configuration contains a valid configuration. o2...15: Reserved. |
|
2 |
Get |
Configuration Capability |
DWORD |
Bit level |
o0: BOOTP Client o2: DHCP Client o4: Configuration Settable o6: Interface Configuration change requires reset o7: Acd Capable All other bits are reserved and set to 0. |
|
3 |
Get |
Configuration |
DWORD |
Bit level |
o0: The interface configuration is valid. o1: The interface configuration is obtained with BOOTP. o2: The interface configuration is obtained with DHCP. o3: Reserved All other bits are reserved and set to 0. |
|
4 |
Get |
Physical Link |
UINT |
Path size |
Number of 16 bits word in the element path |
|
5 |
Get |
Interface configuration |
UDINT |
IP Address |
– |
|
UDINT |
Network Mask |
– |
|||
|
UDINT |
Gateway Address |
– |
|||
|
UDINT |
Primary Name |
– |
|||
|
UDINT |
Secondary Name |
0: No secondary name server address has been configured. |
|||
|
STRING |
Default Domain Name |
0: No Domain Name is configured |
|||
|
6 |
Get |
Host Name |
STRING |
– |
ASCII characters. 0: No host name is configured |
Ethernet Link Object (Class ID = F6 hex)
This object provides the mechanism to configure a TCP/IP network interface device.
The following table describes the class attributes of the Ethernet Link object:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Value (hex) |
Details |
|---|---|---|---|---|---|
|
1 |
Get |
Revision |
UINT |
4 |
Implementation revision of the Ethernet Link Object |
|
2 |
Get |
Max Instances |
UINT |
3 |
The largest instance number |
|
3 |
Get |
Number of Instances |
UINT |
3 |
The number of object instances |
The following table describes the Class Services:
|
Service Code (hex) |
Name |
Description |
|---|---|---|
|
01 |
Get Attribute All |
Returns the value of all class attributes |
|
0E |
Get Attribute Single |
Returns the value of the specified attribute |
Instance Codes
Only instance 1 is supported.
The following table describes the Instance Services:
|
Service Code (hex) |
Name |
Description |
|---|---|---|
|
01 |
Get Attribute All |
Returns the value of all instance attributes |
|
0E |
Get Attribute Single |
Returns the value of the specified instance attribute |
The following table describes the Instance attributes:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Value |
Description |
|---|---|---|---|---|---|
|
1 |
Get |
Interface Speed |
UDINT |
– |
Speed in Mbit/s (10 or 100) |
|
2 |
Get |
Interface Flags |
DWORD |
Bit level |
o0: Link status o1: Half/full duplex o2...4: Negotiation status o5: Manual setting / requires reset o6: Local hardware error detected All other bits are reserved and set to 0. |
|
3 |
Get |
Physical Address |
ARRAY of 6 USINT |
– |
This array contains the MAC address of the product. Format: XX-XX-XX-XX-XX-XX |
EtherNet/IP Interface Diagnostic Object (Class ID = 350 hex)
The following table describes the class attributes of the EtherNet/IP Interface Diagnostic object:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Value (hex) |
Details |
|---|---|---|---|---|---|
|
1 |
Get |
Revision |
UINT |
01 |
Increased by 1 on each new update of the object |
|
2 |
Get |
Max Instance |
UINT |
01 |
Maximum instance number of the object |
The following table describes the instance attributes of the EtherNet/IP Interface Diagnostic object:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Details |
|---|---|---|---|---|
|
1 |
Get |
Protocols supported |
UINT |
Protocol(s) supported (0=not supported, 1=supported): oBit 0: EtherNet/IP oBit 1: Modbus TCP oBit 2: Modbus Serial oBits 3...15: Reserved, 0 |
|
2 |
Get |
Connection Diag |
STRUCT of |
|
|
Max CIP IO Connections opened |
UINT |
Maximum number of CIP I/O connections opened. |
||
|
Current CIP IO Connections |
UINT |
Number of CIP I/O connections currently opened. |
||
|
Max CIP Explicit Connections opened |
UINT |
Maximum number of CIP explicit connections opened. |
||
|
Current CIP Explicit Connections |
UINT |
Number of CIP explicit connections currently opened |
||
|
CIP Connections Opening Errors |
UINT |
Incremented on each unsuccessful attempt to open a CIP connection. |
||
|
CIP Connections Timeout Errors |
UINT |
Incremented when a CIP connection is timed out. |
||
|
Max EIP TCP Connections opened |
UINT |
Maximum number of TCP connections opened and used for EtherNet/IP communication. |
||
|
Current EIP TCP Connections |
UINT |
Number of TCP connections currently open and being used for EtherNet/IP communication. |
||
|
3 |
Get Clear |
IO Messaging Diag |
STRUCT of |
|
|
IO Production Counter |
UDINT |
Incremented each time a Class 0/1 CIP message is sent. |
||
|
IO Consumption Counter |
UDINT |
Incremented each time a Class 0/1 CIP message is received. |
||
|
IO Production Send Errors Counter |
UINT |
Incremented each Time a Class 0/1 message is not sent. |
||
|
IO Consumption Receive Errors Counter |
UINT |
Incremented each time a consumption is received that contains an error. |
||
|
4 |
Get Clear |
Explicit Messaging Diag |
STRUCT of |
|
|
Class3 Msg Send Counter |
UDINT |
Incremented each time a Class 3 CIP message is sent. |
||
|
Class3 Msg Receive Counter |
UDINT |
Incremented each time a Class 3 CIP message is received. |
||
|
UCMM Msg Send Counter |
UDINT |
Incremented each time a UCMM message is sent. |
||
|
UCMM Msg Receive Counter |
UDINT |
Incremented each time a UCMM message is received. |
||
IO Connection Diagnostic Object (Class ID = 352 hex)
The following table describes the class attributes of the IO Connection Diagnostic object:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Value (hex) |
Details |
|---|---|---|---|---|---|
|
1 |
Get |
Revision |
UINT |
01 |
Increased by 1 on each new update of the object. |
|
2 |
Get |
Max Instance |
UINT |
01 |
Maximum instance number of the object 0...n where n is the maximum number of CIP I/O connections. NOTE: There is an IO Connection Diagnostic object instance for both O->T and T->O paths. |
The following table describes the instance attributes of the I/O Connection Diagnostic object:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Details |
|---|---|---|---|---|
|
1 |
Get Clear |
IO Com Diag |
STRUCT of |
|
|
IO Production Counter |
UDINT |
Incremented each time a production is sent. |
||
|
IO Consumption Counter |
UDINT |
Incremented each time a consumption is received. |
||
|
IO Production Send Errors Counter |
UINT |
Incremented each time a production is not sent due to an error. |
||
|
IO Consumption Receive Errors Counter |
UINT |
Incremented each time a consumption is received that contains an error. |
||
|
CIP Connection TimeOut Errors |
UINT |
Incremented each time a connection is timed out. |
||
|
CIP Connection Opening Errors |
UINT |
Incremented on each unsuccessful attempt to open a connection. |
||
|
CIP Connection State |
UINT |
State of the CIP IO connection. |
||
|
CIP Last Error General Status |
UINT |
General status of the last error detected on the connection. |
||
|
CIP Last Error Extended Status |
UINT |
Extended status of the last error detected on the connection. |
||
|
Input Com Status |
UINT |
Communication status of the inputs. |
||
|
Output Com Status |
UINT |
Communication status of the outputs. |
||
|
2 |
Get |
Connection Diag |
STRUCT of |
|
|
Production Connection ID |
UDINT |
Connection ID for production. |
||
|
Consumption Connection ID |
UDINT |
Connection ID for consumption. |
||
|
Production RPI |
UDINT |
Requested Packet Interval (RPI) for productions, in μs. |
||
|
Production API |
UDINT |
Actual Packet Interval (API) for productions. |
||
|
Consumption RPI |
UDINT |
RPI for consumptions. |
||
|
Consumption API |
UDINT |
API for consumptions. |
||
|
Production Connection Parameters |
UDINT |
Connection parameters for productions. |
||
|
Consumption Connection Parameters |
UDINT |
Connection parameters for consumptions. |
||
|
Local IP |
UDINT |
Local IP address for I/O communication. |
||
|
Local UDP Port |
UINT |
Local UDP port number for I/O communication. |
||
|
Remote IP |
UDINT |
Remote IP address for I/O communication. |
||
|
Remote UDP Port |
UINT |
Remote UDP port number for I/O communication. |
||
|
Production Multicast IP |
UDINT |
Multicast IP address for productions, or 0 if multicast is not used. |
||
|
Consumption Multicast IP |
UDINT |
Multicast IP address for consumptions, or 0 if multicast is not used. |
||
|
Protocols supported |
UINT |
Protocol(s) supported (0 = not supported, 1=supported): oBit 0: EtherNet/IP oBit 1: Modbus TCP oBit 2: Modbus Serial oBits 3...15: Reserved, 0 |
||
Instance Attributes
The following table describes the Class Services:
|
Service Code (hex) |
Name |
Description |
|---|---|---|
|
01 |
Get_Attributes_All |
Returns the value of all class attributes. |
|
0E |
Get_Attribute_Single |
Returns the value of a specified attribute. |
|
4C |
Get_and_Clear |
Gets and clears a specified attribute. |
Explicit Connection Diagnostic Object (Class ID = 353 hex)
The following table describes the class attributes of the Explicit Connection Diagnostic object:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Value (hex) |
Details |
|---|---|---|---|---|---|
|
1 |
Get |
Revision |
UINT |
01 |
Increased by 1 at each new update of the object. |
|
2 |
Get |
Max Instance |
UINT |
0...n (maximum number of CIP IO connections) |
Maximum instance number of the object. |
The following table describes the instance attributes of the Explicit Connection Diagnostic object:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Details |
|---|---|---|---|---|
|
1 |
Get |
Originator Connection ID |
UDINT |
O to T Connection ID |
|
2 |
Get |
Originator IP |
UDINT |
– |
|
3 |
Get |
Originator TCP Port |
UINT |
– |
|
4 |
Get |
Target Connection ID |
UDINT |
T to O Connection ID |
|
5 |
Get |
Target IP |
UDINT |
– |
|
6 |
Get |
Target TCP Port |
UINT |
– |
|
7 |
Get |
Msg Send Counter |
UDINT |
Incremented each time a Class 3 CIP Message is sent on the connection |
|
8 |
Get |
Msg ReceiveCounter |
UDINT |
Incremented each time a Class 3 CIP Message is received on the connection |
Explicit Connections Diagnostic List Object (Class ID = 354 hex)
The following table describes the class attributes of the Explicit Connections Diagnostic List object:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Value (hex) |
Details |
|---|---|---|---|---|---|
|
1 |
Get |
Revision |
UINT |
01 |
Increased by 1 at each new update of the object. |
|
2 |
Get |
Max Instance |
UINT |
02 |
Maximum number of concurrent list accesses supported. |
The following table describes the instance attributes of the Explicit Connections Diagnostic List object:
|
Attribute ID (hex) |
Access |
Name |
Data Type |
Details |
|---|---|---|---|---|
|
1 |
Get |
Number of Connections |
UINT |
Total number of open Explicit connections |
|
2 |
Get |
Explicit Messaging Connections Diagnostic List |
ARRAY of STRUCT |
Contents of instantiated Explicit Connection Diagnostic objects |
|
Originator Connection ID |
UDINT |
Originator to Target connection ID |
||
|
Originator IP |
UDINT |
Originator to Target IP address |
||
|
Originator TCP Port |
UINT |
Originator to Target port number |
||
|
Target Connection ID |
UDINT |
Target to Originator connection ID |
||
|
Target IP |
UDINT |
Target to Originator IP address |
||
|
Target TCP Port |
UINT |
Target to Originator port number |
||
|
Msg Send Counter |
UDINT |
Incremented each time a Class 3 CIP message is sent on the connection |
||
|
Msg Receive Counter |
UDINT |
Incremented each time a Class 3 CIP message is sent on the connection |
The following table describes the Class Services:
|
Service Code (hex) |
Name |
Description |
|---|---|---|
|
08 |
Create |
Creates an instance of the Explicit Connections Diagnostic List object. |
|
09 |
Delete |
Deletes an instance of the Explicit Connections Diagnostic List object. |