TM5CAI8O8CVL General Description
The following figure shows the electronic modules of the TM5CAI8O8CVL:
N° |
Designation |
Refer to |
---|---|---|
1 |
Analog Input electronic module / 4 Analog Inputs |
|
2 |
Analog Input electronic module / 4 Analog Inputs |
|
3 |
Dummy Module |
|
4 |
Analog Output electronic module / 4 Analog Outputs |
|
5 |
Analog Output electronic module / 4 Analog Outputs |
|
UNINTENDED EQUIPMENT OPERATION |
Do not exceed any of the rated values specified in the environmental and electrical characteristics tables. |
Failure to follow these instructions can result in death, serious injury, or equipment damage. |
The following table provides the general characteristics of the TM5CAI8O8CVL module:
General characteristics |
|
---|---|
Rated power supply voltage Power supply source |
24 Vdc Connected to the 24 Vdc I/O power segment |
Power supply range |
20.4...28.8 Vdc |
24 Vdc I/O power segment current draw |
214 mA |
TM5 Bus 5 Vdc current draw |
50 mA |
Power dissipation |
5.25 W |
Weight |
250 g (8.82 oz) |
Id code for firmware update |
50663 |
See also Environmental Characteristics.