EcoStruxure Machine Expert version 1.1 does not support the M238, M258, LMC058 and LMC078 controllers.

TM5SPS3 Wiring Diagram

Wiring Diagram

The following figure shows the wiring diagram for the TM5SPS3 interface power distribution module:

G-SE-0036013.1.gif-high.gif

 

(A)   Interface Power Distribution Module (IPDM)

(1)   Internal electronics

(2)   24 Vdc I/O power segment integrated in the bus bases

(3)   PS1/PS2: External isolated power supply 24 Vdc

(4)   External fuse, Type T slow blow, 10 A max., 250 V

(5)   External fuse, Type T slow blow, 1 A, 250 V

Warning_Color.gifWARNING

POTENTIAL OF OVERHEATING AND FIRE

oDo not connect the modules directly to line voltage.

oUse only isolating PELV systems according to IEC 61140 to supply power to the modules.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Warning_Color.gifWARNING

UNINTENDED EQUIPMENT OPERATION

Do not connect wires to unused terminals and/or terminals indicated as “No Connection (N.C.)”.

Failure to follow these instructions can result in death, serious injury, or equipment damage.