EcoStruxure Machine Expert version 1.1 does not support the M238, M258, LMC058 and LMC078 controllers.

TM7BAI4PLA Characteristics

General Characteristics

Danger_Color.gifDANGER

POTENTIAL FOR EXPLOSION

oOnly use this equipment in non-hazardous locations or in locations that comply either with the Class I, Division 2, Groups A, B, C and D, or with the ATEX Group II, Zone 2 specifications for hazardous locations, depending on your local and/or national regulations.

oDo not substitute components which would impair compliance to the hazardous location specifications of this equipment.

oDo not connect or disconnect equipment unless power has been removed or the location is known to be non-hazardous.

Failure to follow these instructions will result in death or serious injury.

NOTE: Additional equipment used in conjunction with the equipment described herein must also be suitable for the operating location.

Danger_Color.gifDANGER

FIRE HAZARD

Use cable sizes that meet the I/O channel and power supply voltage and current ratings.

Failure to follow these instructions will result in death or serious injury.

Warning_Color.gifWARNING

UNINTENDED EQUIPMENT OPERATION

Do not exceed any of the rated values specified in the environmental and electrical characteristics tables.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

The table below provides the general characteristics of the TM7BAI4PLA block:

General characteristics

Rated power supply voltage

24 Vdc

Power supply range

18...30 Vdc

24 Vdc I/O power segment current draw

108 mA

TM7 power bus current draw

38 mA

Protection

Against reverse polarity

Power dissipation

3.4 W max.

Weight

200 g (7.05 oz.)

ID code

5254 dec

See also Environmental Characteristics.

Input Characteristics

The table below provides the input characteristics of the TM7BAI4PLA block:

Input characteristics

Input sensor type

Thermocouple

Input temperature range

Type J: -210...1200°C (-344...2192°F)

Type K: -270...1372°C (-454...2501°F)

Type S: -50...1768°C (-56...3214°F)

Input voltage range (software configurable)

1st mode: ± 65.534 mV

2nd mode: ± 32.765 mV

Sample duration time

62 ms per input (with 50 Hz filter)

Sample duration time for terminal temperature measurement

62 ms (with 50 Hz filter)

Conversion mode

Sigma delta type

Linearization mode

Software

Input filter

Cut-off frequency

Low pass 1st order / 4 Hz

Attenuation

20 dB

Filter time

2...20 ms using configuration software

Input time

1...66.7 ms configured by software

Input tolerance - maximum deviation at ambient 25°C (77°F)

Type J: ± 0.064% of the measurement

Type K: ± 0.07% of the measurement

Type S: ± 0.128% of the measurement

Input tolerance - temperature drift

0.0123% / °C (0.006% / °F) of the measurement

Input tolerance - non linearity

± 0.002% of the entire measurement range

Input tolerance - terminal temperature compensation

± 2°C (35.6°F) after 10 mn

Digital resolution

16-bit

Resolution value

65536 increments

Resolution temperature value

0.1°C (0.18°F)

Resolution voltage value

1st mode: 2 µV

2nd mode: 1 µV

Common mode rejection

DC

70 dB min.

50 Hz

70 dB min.

Crosstalk rejection between channels

70 dB min.

Isolation between channels

Not isolated

Isolation between channels and bus

See note 1

Permitted input signal

±30 Vdc max.

Input protection

Protection against wiring with 24 Vdc supply voltage

1 The isolation of the block is 500 Vac RMS between the electronics powered by the TM7 power bus and those powered by the 24 Vdc I/O power segment connected to the block. In practice, there is a bridge between the TM7 power bus and the 24 Vdc I/O power segment. The two power circuits reference the same functional ground (FE) through specific components designed to reduce effects of electromagnetic interference. These components are rated at 30 Vdc or 60 Vdc. This effectively reduces isolation of the entire system from the 500 Vac RMS.

TM7ACTHA Characteristics

The table below provides the TM7ACTHA thermocouple plug characteristics:

TM7ACTHA thermocouple plug characteristics

Connector type

M12, A coded 5-pin, male, straight connector type

Compensation sensor

PT1000

Internal terminal type

Screw