EcoStruxure Machine Expert version 1.1 does not support the M238, M258, LMC058 and LMC078 controllers.

Physical Description

Introduction

The TM7 System consists of IP67 I/O blocks along with field bus, expansion, sensor/actuator and power cables.

A TM7 I/O block can be a:

odigital I/O block,

oanalog I/O block, for details, refer to the Modicon TM7 Analog I/O Blocks Hardware Guide

oPower Distribution Block (PDB), for details, refer to the chapter TM7SPS1A Power Distribution Block (PDB) in the Modicon TM5 / TM7 Flexible System - System Planning and Installation Guide

General View of a TM7 I/O Block and Cables

The following figure shows a TM7 I/O block and associated cables:

G-SE-0006162.1.gif

 

 

Item

TM7 Cable Type

TM7 Block Connector

A

Expansion bus drop cable

TM7 bus IN

B

Expansion bus drop cable

TM7 bus OUT

1...4

Sensor or actuator cable

I/O connectors

C

Power drop cable

24 Vdc power IN connector

D

Power drop cable

24 Vdc power OUT connector

Warning_Color.gifWARNING

IP67 NON-CONFORMANCE

oProperly fit all connectors with cables or sealing plugs and tighten for IP67 conformance according to the torque values as specified in this document.

oDo not connect or disconnect cables or sealing plugs in the presence of water or moisture.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTICE

ELECTROSTATIC DISCHARGE

oDo not touch the pin connectors of the block.

oKeep the cables or sealing plugs in place during normal operation.

Failure to follow these instructions can result in equipment damage.

TM7 Cables References

Refer to TM7 Cables, for more information on the type and length of cables, along with their references.

TM7 I/O Blocks Pin and Connector Assignments

The following figure shows the connector assignments of a TM7 I/O block:

G-SE-0006159.1.gif-high.gif

 

(A)   TM7 bus IN connector M12

(B)   TM7 bus OUT connector M12

(C)   24 Vdc power IN connector M8

(D)   24 Vdc power OUT connector M8

The following figure shows the pin assignments of the TM7 bus IN (A) and OUT (B) connectors:

Connection

Pin

Designation

G-SE-0006160.1.gif

 

 

1

TM7 V+

2

TM7 Bus Data

3

TM7 0 Vdc

4

TM7 Bus Data

5

N.C.

The following figure shows the pin assignments of the 24 Vdc power IN (C) and OUT (D) connectors:

Connection

Pin

Designation

G-SE-0006446.1.gif

 

 

1

24 Vdc I/O power segment

2

24 Vdc I/O power segment

3

0 Vdc

4

0 Vdc

NOTE:

oThe status of the LEDs are provided in the Presentation section of each I/O block.

oThe pin assignments of the I/O connectors are provided in the Wiring Diagram section of each I/O block.