Ejemplo de postconfiguración

Ejemplo de archivo de postconfiguración

# TM262M25MESS8T / Ethernet_1 / IPAddress

# Ethernet IP address

id[45000].pos[5].id[111].param[0] = [192, 168, 1, 3]]

 

# TM262M25MESS8T / Ethernet_1 / SubnetMask

# Ethernet IP mask

id[45000].pos[5].id[111].param[1] = [255, 255, 255, 0]]

 

# TM262M25MESS8T / Ethernet_1 / GatewayAddress

# Ethernet IP gateway address

id[45000].pos[5].id[111].param[2] = [0, 0, 0, 0]]

 

# TM262M25MESS8T / Ethernet_1 / IPConfigMode

# IP configuration mode: 0:FIXED 1:BOOTP 2:DHCP

id[45000].pos[5].id[111].param[4] = 0

 

# TM262M25MESS8T / Ethernet_1 / DeviceName

# Name of the device on the Ethernet network

id[45000].pos[5].id[111].param[5] = 'my_Device'

 

# TM262M25MESS8T / Ethernet_2 / IPAddress

# Ethernet IP address

id[45000].pos[6].id[45111].param[0] = [192, 168, 102, 2]

 

# TM262M25MESS8T / Ethernet_2 / SubnetMask

# Ethernet IP mask

id[45000].pos[6].id[45111].param[1] = [255, 255, 255, 0]

 

# TM262M25MESS8T / Ethernet_2 / GatewayAddress

# Ethernet IP gateway address

id[45000].pos[6].id[45111].param[2] = [0, 0, 0, 0]

 

# TM262M25MESS8T / Ethernet_2 / IPConfigMode

# IP configuration mode: 0:FIXED 1:BOOTP 2:DHCP

id[45000].pos[6].id[45111].param[4] = 0

 

# TM262M25MESS8T / Ethernet_2 / DeviceName

# Name of the device on the Ethernet network

id[45000].pos[6].id[45111].param[5] = 'my_Device'

 

# TM262M25MESS8T / Serial_Line / Serial Line Configuration / Baudrate

# Serial Line Baud Rate in bit/s

id[45000].pos[7].id[40101].param[10000].Bauds = 19200

 

# TM262M25MESS8T / Serial_Line / Serial Line Configuration / Parity

# Serial Line Parity (0=None, 1=Odd, 2=Even)

id[45000].pos[7].id[40101].param[10000].Parity = 2

 

# TM262M25MESS8T / Serial_Line / Serial Line Configuration / DataBits

# Serial Line Data bits (7 or 8)

id[45000].pos[7].id[40101].param[10000].DataFormat = 8

 

# TM262M25MESS8T / Serial_Line / Serial Line Configuration / StopBits

# Serial Line Stop bits (1 or 2)

id[45000].pos[7].id[40101].param[10000].StopBit = 1