Baud Rate (Transmission Speed)
The baud rate must be adjusted to your application.
For selecting the baud rate, take the following criteria into account:
oAll network devices must be set to operate on the same baud rate.
oThe maximum bus length correlates with the baud rate.
To modify the baud rate, double-click the CAN_Layer node in the Devices tree and adapt the Baudrate (bits/s) value in the General tab.
The ARMIO board supports the following baud rates:
|
Baud rate (bits/s) |
Maximum bus length (m) |
DIP switch 6 |
DIP switch 7 |
|---|---|---|---|
|
20000 |
2500 |
Off |
Off |
|
125000 |
500 |
On |
Off |
|
500000 |
100 |
Off |
On |
|
1000000 |
20 |
On |
On |
NOTE: On the ARMIO board, the baud rate can be configured with the DIP switches 6 and 7.