The maintenance intervals may have to be adapted to the greatly varying operational hours depending on the application.
For procedures to replace the different parts, refer to Replacing Parts.
Perform the following maintenance tasks after delivery:
Date |
Action |
---|---|
After two months of service life |
oVerify the actuator by visual inspection for any damage or missing parts, especially for moving parts and parts at risk for collisions such as mounting elements. |
Perform the following maintenance tasks within the stated intervals:
Interval |
Action |
---|---|
Every 500 hours of operation or when the travel path(1) is reached |
oClean the actuator if necessary. oLubricate the actuator. For further information, refer to Lubricating the Actuator. |
Every 2,000 hours of operation or when the travel path is reached four times |
oVerify the toothed belt abrasion and replace the toothed belt, if necessary. oVerify the actuator by visual inspection for any damage or missing parts. Especially moving parts and parts at risk for collisions such as mounting elements. oVerify the sensors for functionality. oVerify all parts for bolted connections. |
Annually or after an uncontrolled stop (stop category 0) |
oVerify the brake function during operations. For further information, refer to the corresponding motor manual of the optionally pre-installed Schneider Electric motor. |
Every 20,000 hours of operation |
oReplace the optionally pre-installed Schneider Electric motor. For further information, refer to the corresponding motor manual of the motor. |
Every four years after the date of manufacturing (DOM) |
oIf a belt drive is installed: Replace the toothed belt as a precautionary measure. |
(1) For the travel path at normal ambient conditions, refer to Unimotion Maintenance- and Assembly Instructions PNCE Electric Cylinder. |
NOTE: The ball bearings are lubricated for life.