Commissioning the HoistDutyRating Function Block
Step |
Action |
---|---|
1 |
Instantiate the HoistDutyRating function block. |
2 |
Enter the value of the nominal load (i_rLoadNom) and the inputs coming from the field: drive run discrete signal (i_xDrvRun) and actual load value (i_rLoadAct). |
3 |
Make sure that the 3 variables connected to the input/output pins (iq_arMeanEffectLoad, iq_alrRunTime, iq_stHoistDutyCtrl) of the function block are defined as either persistent or retained. |
4 |
Verify the accuracy of the actual load value during commissioning and maintenance cycles. |