Removal of the Optional Module (No Replacement)

Required Tool for Removal of the Optional Module

Module part

Tool

Module shaft

Cross slot maximum PH1

How to Disassemble the Optional Module

Step

Action

1

Set main switch to OFF position, or otherwise disconnect all power to the system.

2

Prevent main switch from being switched back on.

3

Undo the two M3x6 screws on the module shaft.

4

Withdraw the module from the cartridge.

Result: The module is deinstalled now and the module shaft is empty.

5

Screw the blanking plate onto the empty module shaft.

Result: The empty module shaft is closed by the blanking plate.

NOTICE

INOPERABLE EQUIPMENT

Do not remove the optional module when the controller is under power.

Failure to follow these instructions can result in equipment damage.