8342 On/OffPos inverted (On/OffDelay ok?)

Description

Refer to Diagnostic class (standard): 3

CamSwitch.OnPosition and CamSwitch.OffPosition switched their relative position due to velocity compensation with the configured delay

Cause

Solution

CamSwitch.OnPosition and CamSwitch.OffPosition are too close together for the present speed and the difference of the entered delay times of the corresponding CamTrack.OnDelay and CamTrack.OffDelay.

oReduce velocity.

oReduce delay difference.

oIncrease position difference.