8732 Slave not responding

Description

Refer to Diagnostic class (standard): 3

Slave with bus address preceded by SI= is not exchanging cyclical I/O data. The error code specified after Err= corresponds to the error code of the ErrorCode parameter.

If the Activation parameter is set to false, then this diagnostic message is not triggered.

Cause

Solution

Slave has been disabled.

Reactivate slave.

At least one slave is not configured correctly.

Verify and correct if necessary the configuration.

Detected wiring error: Cable error in PROFIBUS DP.

Verify and correct or replace if necessary the cable.

Detected wiring error: Incorrect bus topology.

Verify and correct or replace if necessary the terminals, transmission lines, and so on.