8997 Parameter MotorIdentification invalid
Refer to Diagnostic class (standard): 3
Default reaction |
||
---|---|---|
AD |
AD |
|
- |
- |
The parameter MotorIdentification has an invalid value.
Cause |
Solution |
---|---|
The parameter is set to Motor with nameplate / 0, but the electronic motor nameplate is saved in the servo amplifier. |
oVerify and correct if necessary the axis assignment in the PLC configuration. oSet parameter to Motor without nameplate / 1. |
The parameter is set to Motor without nameplate / 1 but the electronic motor nameplate is saved in the encoder EEPROM of the motor. |
oVerify whether the Encoder is connected and correct it if necessary. oVerify and correct if necessary the axis assignment in the PLC configuration. oSet parameter to Motor without nameplate / 0. |