8101 Power stage overtemperature
Refer to Diagnostic class (standard): 3
Default reaction |
||
---|---|---|
BD2 |
CD |
|
– |
– |
The cooling element of the PacDrive servo amplifier is too hot.
Cause |
Solution |
---|---|
Insufficient ventilation or ambient temperature too high. |
oVerify and correct if necessary the device fans and ventilation slots (if available). oVerify and correct if necessary the ventilation in switching cabinet. oIf installed, ensure that the air conditioning unit is functioning properly. |
The power stage or the power rectifier is overloaded. |
oVerify and correct if necessary the combination motor / drive. oVerify and correct if necessary the calculation of motor and drive. |
Detected hardware error: The temperature sensor is inoperable. |
Replace the device. |