8142 Control board overtemperature
Refer to Diagnostic class (standard): 3
Default reaction |
||
---|---|---|
BD2 |
CD |
|
BP1 |
BP1 |
The temperature of the power board inside the housing is too high.
Cause |
Solution |
---|---|
Insufficient ventilation or ambient temperature too high. |
oVerify and correct if necessary the ventilation in the control cabinet. oIf installed, ensure that the air conditioning unit is functioning properly. |
Detected hardware error: The temperature sensor is inoperable. |
Replace the device. |