8165 Sercos Slave C2D warning detected

Description

Refer to Diagnostic class (standard): 2

Reaction: Manufacturer-specific

The following diagnostic message is triggered by the following objects:

oSercos drive

oTM5NS31 (S3IO)

oSafe Logic Controller

The extended diagnostic message (ExtDiagMsg) can be displayed in two different formats:

oDiag = 16#aaaa with aaaa is the error code from Sercos IDN S-0-0012.

Refer to the Sercos C2D Error Messages for details.

oDiag = 0xaaaaaaaa with aaaaaaaa corresponds to the diagnostic message from the parameter DiagnosticNumber (Sercos IDN S-0-0390).

Sercos C2D Error Messages

Format of the ExtDiagMsg: Diag 0 16#aaaa with aaaa is the error code from Sercos IDN S-0-0012.

A Sercos alert of the diagnostic class 2 (C2D) has been detected. The extended diagnostic contains a data word that provides information on the cause.

The individual bits of this data word have the following meanings:(Sercos C2D alert (Assignment according to the Sercos specification IDN S-0-0012)):

Bit

Meaning

Bit 0

Overload alert

Bit 1

Amplifier overtemperature alert

Bit 2

Motor overtemperature alert

Bit 3

Cooling error alert

Bit 4

Reserved

Bit 5

Feedback error

Bit 6

Reserved

Bit 7

Reserved

Bit 8

Reserved

Bit 9

Undervoltage error

Bit 10

Reserved

Bit 11

Excessive velocity deviation

Bit 12

Reserved

Bit 13

Target position outside of travel range

Bit 14

Reserved

Bit 15

Manufacturer-specific error (refer to diagnostic message 8166)