FB_MultiBelt - General Information
Type: |
Function block |
Available as of: |
V1.0.0.0 |
Inherits from: |
- |
Implements: |
- |
Versions: |
Current version |
Processing several trains in a MultiBelt network. The function block replaces and enhances DualBelt functionality and can be used for the infeed or grouping of products.
Using this module, several belts processing parallel can be processed with the trains mounted on them. Stations can be defined where the trains can pick up or deliver the products. See Basics for a detailed description of the function and the options.
NOTE: Only Controller OnBoard I/O touch probes and drive touch probes are supported by the functionalities of this library. TM5 module touch probes are not supported.
Input |
Data type |
Description |
---|---|---|
i_xEnable |
BOOL |
A rising edge FALSE -> TRUE activates the POU, a falling edge TRUE -> FALSE deactivates the POU. A deactivated POU does not execute any actions. |
i_xStart |
BOOL |
FALSE -> TRUE: Start of the MultiBelt network according to the set parameters. |
i_xWSSelect |
BOOL |
TRUE: Warm start is selected. With a positive edge on i_xStart, a warm start is performed first. |
Output |
Data type |
Description |
---|---|---|
q_xActive |
BOOL |
TRUE: The POU is active and has to be executed further. FALSE: The POU is inactive. |
q_xReady |
BOOL |
TRUE: The POU is ready to operate and can accept user commands. FALSE: The POU is not ready to accept user commands. |
q_etDiag |
General library-independent statement on the diagnostic. A value unequal to GD.ET_Diag.Ok corresponds to a diagnostic message. |
|
q_etDiagExt |
POU-specific output on the diagnostic. q_etDiag = GD.ET_Diag.Ok -> status message q_etDiag <> GD.ET_Diag.Ok -> diagnostic message |
|
q_sMsg |
STRING[80] |
Event-triggered message which gives more detailed information on the diagnostic state. |
Input/Output |
Data type |
Description |
---|---|---|
iq_stMultiBelt |
Parameter structure of the MultiBelt network |
q_etDiag |
q_etDiagExt |
Enumeration value |
Description |
---|---|---|---|
OK |
9 |
All trains were stopped. |
|
OK |
8 |
The MultiBelt is in automatic mode. |
|
OK |
0 |
The POU is disabled. |
|
OK |
91 |
The POU is being initialized. |
|
OK |
15 |
Wait until all the trains are deactivated. |
|
OK |
1 |
Wait until all the trains are ready. |
|
OK |
10 |
Wait until all the trains are stopped. |
|
OK |
3 |
Wait until the cold start has been accepted. |
|
OK |
4 |
Wait until the cold start is completed. |
|
OK |
2 |
Waiting for starting command. |
|
OK |
7 |
Wait until all the stations are ready. |
|
OK |
6 |
Wait until the warm start is completed. |
|
ControllerConditionInvalid |
35 |
The interface Timer is invalid. |
|
InputParameterInvalid |
74 |
AdditionalStep is outside the valid range. |
|
InputParameterInvalid |
34 |
The length of the belt is invalid. |
|
InputParameterInvalid |
47 |
BeltLength is outside the valid range. |
|
InputParameterInvalid |
101 |
The ControllerStopInterface is invalid. |
|
InputParameterInvalid |
46 |
CrashDistance is outside the valid range. |
|
InputParameterInvalid |
54 |
The acceleration of the start motion is outside the valid range. |
|
InputParameterInvalid |
55 |
The deceleration of the departure move is outside the valid range. |
|
InputParameterInvalid |
62 |
DepartureDelay is outside the valid range. |
|
InputParameterInvalid |
56 |
The jerk of the start moiton is outside the valid range. |
|
InputParameterInvalid |
53 |
The velocity of the start motion is outside the valid range. |
|
InputParameterInvalid |
26 |
The interface of the axis is invalid. |
|
InputParameterInvalid |
81 |
The axis has not been set. |
|
InputParameterInvalid |
102 |
This feature is not supported at present. For additional information refer to g_sMsg. |
|
InputParameterInvalid |
99 |
The GearFactor is outside its value range |
|
InputParameterInvalid |
30 |
The distance between two trains is invalid. |
|
InputParameterInvalid |
61 |
The help encoder was not set. |
|
InputParameterInvalid |
36 |
The interface Limit is invalid. |
|
InputParameterInvalid |
63 |
LockOutTime is outside the valid range. |
|
InputParameterInvalid |
92 |
lrMasterPeriod is outside its value range |
|
InputParameterInvalid |
93 |
The value of the parameter lrMinProductLength is outside its range. |
|
InputParameterInvalid |
64 |
MinProductTime is outside the valid range. |
|
InputParameterInvalid |
44 |
NumOfBelts is outside the valid range. |
|
InputParameterInvalid |
43 |
NumOfStations is outside the valid range. |
|
InputParameterInvalid |
70 |
NumOfSteps is outside the valid range. |
|
InputParameterInvalid |
94 |
lrPhase is outside its value range |
|
InputParameterInvalid |
71 |
ProductsPerStep is outside the valid range. |
|
InputParameterInvalid |
66 |
ReadyForStepOffset is outside the valid range. |
|
InputParameterInvalid |
80 |
The interface RefActValues is invalid. |
|
InputParameterInvalid |
42 |
The interface SetLimit is invalid. |
|
InputParameterInvalid |
103 |
SkipSteps feature is not supported for synchron stations. |
|
InputParameterInvalid |
78 |
StartAcceptOffset is outside the valid range. |
|
InputParameterInvalid |
98 |
The parameter lrStartDelayDistance is outside its value range. |
|
InputParameterInvalid |
65 |
StartDelayTime is outside the valid range. |
|
InputParameterInvalid |
79 |
StationLockOffset is outside the valid range. |
|
InputParameterInvalid |
69 |
StationPos is outside the valid range. |
|
InputParameterInvalid |
58 |
The acceleration of a step is outside the valid range. |
|
InputParameterInvalid |
59 |
The deceleration of a step is outside the valid range. |
|
InputParameterInvalid |
60 |
The jerk of a step is outside the valid range. |
|
InputParameterInvalid |
72 |
Steps is outside the valid range. |
|
InputParameterInvalid |
57 |
The velocity for a step is outside the valid range. |
|
InputParameterInvalid |
75 |
StopDistance is outside the valid range. |
|
InputParameterInvalid |
73 |
The sum of the steps is invalid. |
|
InputParameterInvalid |
95 |
lrSynchronEnd is outside its value range. |
|
InputParameterInvalid |
97 |
The sum of (SynchronStart + SynchronEnd) is outside its value range. |
|
InputParameterInvalid |
96 |
lrSynchronStart is outside its value range. |
|
InputParameterInvalid |
48 |
TrainLength is outside the valid range. |
|
InputParameterInvalid |
31 |
The sequence of the trains is invalid. |
|
InputParameterInvalid |
67 |
TrainsDistanceFactor is outside the valid range. |
|
InputParameterInvalid |
68 |
TrainsDistance is outside the valid range. |
|
InputParameterInvalid |
45 |
TrainsPerBeltRange is outside the valid range. |
|
InputParameterInvalid |
77 |
TrainTimeOut is outside the valid range. |
|
InputParameterInvalid |
100 |
diUserCamId for the law of motion SystemCam is not assigned. |
|
InputParameterInvalid |
51 |
The acceleration for the warm start is outside the valid range. |
|
InputParameterInvalid |
51 |
The deceleration for the warm start is outside the valid range. |
|
InputParameterInvalid |
50 |
The jerk for the warm start is outside the valid range. |
|
InputParameterInvalid |
49 |
The velocity for the warm start is outside the valid range. |
|
InputParameterInvalid |
76 |
Warning distance is outside the valid range. |
|
SercosConditionInvalid |
24 |
The Sercos interface is invalid. |
|
SystemParameterInvalid |
33 |
The cycle time of the RTB is outside the valid range. |
|
UnexpectedProgramBehavior |
22 |
Collision |
|
UnexpectedProgramBehavior |
23 |
Diagnostic message of the Smg. |
|
UnexpectedProgramBehavior |
39 |
A train is moving backwards. |
|
UnexpectedProgramBehavior |
25 |
Indeterminable state. |
|
WarmStartConditionInvalid |
32 |
The position of the train is outside the warm start window. |
|
WarmStartConditionInvalid |
27 |
A warm start is not possible. |
Enumeration name: |
AdditionalStepRange |
Enumeration value: |
74 |
Description: |
AdditionalStep is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].lrAdditionalStep is outside its value range. |
The parameter stMultiBelt.astStation[x].lrAdditionalStep must be in the range >= 0. |
Enumeration name: |
AllTrainsHold |
Enumeration value: |
9 |
Description: |
All trains were stopped. |
Issue |
Cause |
Solution |
---|---|---|
- |
Status message - Stop during automatic mode Input i_xStart = FALSE |
Set the input i_xStart to TRUE. |
Enumeration name: |
Automatic |
Enumeration value: |
8 |
Description: |
The MultiBelt is in automatic mode. |
Automatic mode is active
Enumeration name: |
BeltLengthInvalid |
Enumeration value: |
34 |
Description: |
The length of the belt is invalid. |
Issue |
Cause |
Solution |
---|---|---|
- |
At least one train position is greater than +/-stGeneral.lrBeltLength |
The trains must be homed. Adjust the parameter stMultiBelt.stGeneral.lrBeltLength. |
Enumeration name: |
BeltLengthRange |
Enumeration value: |
47 |
Description: |
BeltLength is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.stGeneral.lrBeltLength is outside its value range. |
The parameter stMultiBelt.stGeneral.lrBeltLength must be in the range > 0. |
ControllerStopInterfaceInvalid
Enumeration name: |
ControllerStopInterfaceInvalid |
Enumeration value: |
101 |
Description: |
The ControllerStopInterface is invalid. |
Issue |
Cause |
Solution |
---|---|---|
- |
ControllerStop interface invalid |
Incorrect drive type |
Enumeration name: |
Crash |
Enumeration value: |
22 |
Description: |
Collision |
Issue |
Cause |
Solution |
---|---|---|
- |
The collision monitoring has detected critical distances between the trains and stopped. |
Verify parameterization of the stations and trains. Verify parameter stMultiBelt.stGeneral.lrCrashDistance. |
Enumeration name: |
CrashDistanceRange |
Enumeration value: |
46 |
Description: |
CrashDistance is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.stGeneral.lrCrashDistance is outside its value range. |
The parameter stMultiBelt.stGeneral.lrCrashDistance must be in the range > - stMultiBelt.stGeneral.lrBeltLength. |
Enumeration name: |
CycleTimeDiag |
Enumeration value: |
33 |
Description: |
The cycle time of the RTB is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The RTB cycle time must be less than the cycle time of the task. |
Decrease the RTB cycle time. Increase the task cycle time. |
Enumeration name: |
DepartureAccelerationRange |
Enumeration value: |
54 |
Description: |
The acceleration of the start motion is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stIndexed.stDepartureMove.lrAcc is outside its value range. |
The parameter stMultiBelt.astStation[x].stIndexed.stDepartureMove.lrAcc must be in the range between Gc_lrMinAcceleration and the smallest MaxAcc of all trains. |
Enumeration name: |
DepartureDecelerationRange |
Enumeration value: |
55 |
Description: |
The deceleration of the departure move is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stIndexed.stDepartureMove.lrDec is outside its value range. |
The parameter stMultiBelt.astStation[x].stIndexed.stDepartureMove.lrDec must be in the range between Gc_lrMinDeceleration and the smallest MaxAcc of all trains. |
Enumeration name: |
DepartureDelayRange |
Enumeration value: |
62 |
Description: |
DepartureDelay is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[iStation].stIndexed.lrDepartureDelay is outside its value range. |
The parameter stMultiBelt.astStation[iStation].stIndexed.lrDepartureDelay must be in the range 0 to stMultiBelt.astStation[iStation].stIndexed.lrStartDelayTime. |
Enumeration name: |
DepartureJerkRange |
Enumeration value: |
56 |
Description: |
The jerk of the start moiton is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stIndexed.stDepartureMove.lrJerk is outside the valid range. |
The parameter stMultiBelt.astStation[x].stIndexed.stDepartureMove.lrJerk must be in the range > Gc_lrMinJerk. |
Enumeration name: |
DepartureVelocityRange |
Enumeration value: |
53 |
Description: |
The velocity of the start motion is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stIndexed.stDepartureMove.lrVel is outside its value range. |
The parameter stMultiBelt.astStation[x].stIndexed.stDepartureMove.lrVel must be in the range between Gc_lrMinVelocity and the smallest MaxVel of all trains. |
Enumeration name: |
Disabled |
Enumeration value: |
0 |
Description: |
The POU is disabled. |
Issue |
Cause |
Solution |
---|---|---|
- |
Status message - Function block is not activated. The input i_xEnable is FALSE. |
Set the input i_xEnable to TRUE. |
Enumeration name: |
DriveLogAdrInvalid |
Enumeration value: |
26 |
Description: |
The interface of the axis is invalid. |
Issue |
Cause |
Solution |
---|---|---|
- |
The drive interface is invalid |
stMultiBelt.astTrain[x].ifDrive.stLogAdr is not assigned or invalid value. |
Enumeration name: |
DriveNotSet |
Enumeration value: |
81 |
Description: |
The axis has not been set. |
Issue |
Cause |
Solution |
---|---|---|
- |
The drive interface is invalid |
The parameter stMultiBelt.astTrain[x].ifDrive is not assigned. |
Enumeration name: |
FeatureNotSupported |
Enumeration value: |
102 |
Description: |
This feature is not supported at present. For additional information refer to g_sMsg. |
Enumeration name: |
GearFactorRange |
Enumeration value: |
99 |
Description: |
The GearFactor is outside its value range |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.stStation[x].stSynchron.lrGearFactor is outside its value range |
The parameter stMultiBelt.stStation[x].stSynchron.lrGearFactor must be in the range > 0 (Default = 1). |
Enumeration name: |
HomeOffsetInvalid |
Enumeration value: |
30 |
Description: |
The distance between two trains is invalid. |
Issue |
Cause |
Solution |
---|---|---|
- |
The distance between two trains is smaller than the train length |
The trains must be homed. The train positions are lost (retain variables) and must be set again. |
Enumeration name: |
Initializing |
Enumeration value: |
91 |
Description: |
The POU is being initialized. |
The function block is being initialized and thus is not yet ready to receive commands at its inputs.
The function block will signalize that it is ready for operation with the signal q_xReady = TRUE.
Enumeration name: |
LencHelpNotSet |
Enumeration value: |
61 |
Description: |
The help encoder was not set. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter iq_stMultiBelt.astStation[iStation].stIndexed.lencHelp is not set. |
The parameter iq_stMultiBelt.astStation[iStation].stIndexed.lencHelp has to be assigned with a logical encoder from the PLC configuration. |
Enumeration name: |
LimitInterfaceInvalid |
Enumeration value: |
36 |
Description: |
The interface Limit is invalid. |
Issue |
Cause |
Solution |
---|---|---|
- |
Limit interface is invalid |
Incorrect drive type |
Enumeration name: |
LockOutTimeRange |
Enumeration value: |
63 |
Description: |
LockOutTime is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stIndexed.lrLockOutTime is outside its value range. |
The parameter stMultiBelt.astStation[x].stIndexed.lrLockOutTime must be in the range >= 0. |
Enumeration name: |
MasterPeriodeRange |
Enumeration value: |
92 |
Description: |
lrMasterPeriod is outside its value range |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[iStation].stSynchron.lrMasterPeriod is outside its value range. |
The parameter stMultiBelt.astStation[iStation].stSynchron.lrMasterPeriod must be greater than 0. |
Enumeration name: |
MinProductLengthRange |
Enumeration value: |
93 |
Description: |
The value of the parameter lrMinProductLength is outside its range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stSynchron.lrMinProductLength is outside its value range. |
The parameter stMultiBelt.astStation[x].stSynchron.lrMinProductLength must be >= 0. |
Enumeration name: |
MinProductTimeRange |
Enumeration value: |
64 |
Description: |
MinProductTime is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stIndexed.lrMinProductTime is outside its value range. |
The parameter stMultiBelt.astStation[x].stIndexed.lrMinProductTime must be in the range >= 0. |
Enumeration name: |
NumOfBeltsRange |
Enumeration value: |
44 |
Description: |
NumOfBelts is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.stGeneral. uiNumOfBelts is outside its value range. |
The parameter stMultiBelt.stGeneral. uiNumOfBelts must be in the range from 2 to Gc_uiMaxNumberOfBelts. |
Enumeration name: |
NumOfStationsRange |
Enumeration value: |
43 |
Description: |
NumOfStations is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.stGeneral.uiNumOfStations is outside its value range. |
The parameter stMultiBelt.stGeneral.uiNumOfStations must be in the range from 1 to Gc_uiMaxNumberOfStations. |
Enumeration name: |
NumOfStepsRange |
Enumeration value: |
70 |
Description: |
NumOfSteps is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].uiNumOfSteps is outside its value range. |
The parameter stMultiBelt.astStation[x].uiNumOfSteps must be in the range >= 1. |
Enumeration name: |
OutOfWarmStartWindow |
Enumeration value: |
32 |
Description: |
The position of the train is outside the warm start window. |
Issue |
Cause |
Solution |
---|---|---|
- |
During the warm start at least one train is outside the warm start window. |
Enlarge the parameter stMultiBelt.stGeneral.lrWarmStartWindow. Execute a cold start. |
Enumeration name: |
PhaseRange |
Enumeration value: |
94 |
Description: |
lrPhase is outside its value range |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stSynchron.lrPhase is outside its value range. |
The parameter stMultiBelt.astStation[x].stSynchron.lrPhase must be > 0 and < stMultiBelt.astStation[x].stSynchron.lrMasterPeriod. |
Enumeration name: |
ProductsPerStepRange |
Enumeration value: |
71 |
Description: |
ProductsPerStep is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].auiProductsPerStep[y] is outside its value range. |
The parameter stMultiBelt.astStation[x].auiProductsPerStep[y] must be in the range >= 1. |
Enumeration name: |
ReadyForStepOffsetRange |
Enumeration value: |
66 |
Description: |
ReadyForStepOffset is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stIndexed.lrReadyForStepOffset is outside its value range. |
The parameter stMultiBelt.astStation[x].stIndexed.lrReadyForStepOffset must be in the range <= 0. |
Enumeration name: |
RefActValuesInterfaceInvalid |
Enumeration value: |
80 |
Description: |
The interface RefActValues is invalid. |
Issue |
Cause |
Solution |
---|---|---|
- |
RefActValues interface is invalid |
Incorrect drive type |
Enumeration name: |
SercosInterfaceInvalid |
Enumeration value: |
24 |
Description: |
The Sercos interface is invalid. |
Issue |
Cause |
Solution |
---|---|---|
- |
The global Sercos interface is invalid |
Incorrect drive bus or incorrect controller. Contact support |
Enumeration name: |
SetLimitInterfaceInvalid |
Enumeration value: |
42 |
Description: |
The interface SetLimit is invalid. |
Issue |
Cause |
Solution |
---|---|---|
- |
SetLimit interface is invalid |
Incorrect drive type |
SkipStepsNotSupportedForSynchron
Enumeration name: |
SkipStepsNotSupportedForSynchron |
Enumeration value: |
103 |
Description: |
SkipSteps feature is not supported for synchron stations. |
Enumeration name: |
SmgDiag |
Enumeration value: |
23 |
Description: |
Diagnostic message of the Smg. |
Issue |
Cause |
Solution |
---|---|---|
- |
An error has been detected when generating the internal reference values. |
see q_sMsg for more details |
Enumeration name: |
StartAcceptOffsetRange |
Enumeration value: |
78 |
Description: |
StartAcceptOffset is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].lrTrainTimeOut is outside its value range. |
The parameter stMultiBelt.astStation[x].lrTrainTimeOut must be in the range >= 0. |
Enumeration name: |
StartDelayDistanceRange |
Enumeration value: |
98 |
Description: |
The parameter lrStartDelayDistance is outside its value range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stSynchron.lrStartDelayDistance is outside its value range. |
The parameter stMultiBelt.astStation[x].stSynchron.lrStartDelayDistance must be >= 0. If ET_EventTrigger = StartOnSignal then stMultiBelt.astStation[x].stSynchron.lrStartDelayDistance has to be >= (stMultiBelt.astStation[x].stSynchron.lrSynchronStart *2 + stMultiBelt.astStation[x].stSynchron.lrMinProductLength). If ET_EventTrigger = MasterSelectPos then stMultiBelt.astStation[x].stSynchron.lrStartDelayDistance has to be >= stMultiBelt.astStation[x].stSynchron.lrMasterPeriod. |
Enumeration name: |
StartDelayTimeRange |
Enumeration value: |
65 |
Description: |
StartDelayTime is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stIndexed.lrStartDelayTime is outside its value range. |
The parameter stMultiBelt.astStation[x].stIndexed.lrStartDelayTime must be in the range >= 0. |
Enumeration name: |
StationLockOffsetRange |
Enumeration value: |
79 |
Description: |
StationLockOffset is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].lrStationLockOffset is outside its value range. |
The parameter stMultiBelt.astStation[x].lrStationLockOffset must be in the range <= 0. |
Enumeration name: |
StationPosRange |
Enumeration value: |
69 |
Description: |
StationPos is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].lrStationPos is outside its value range. |
The parameter stMultiBelt.astStation[x].lrStationPos must be in the range <= stMultiBelt.stGeneral.lrBeltLength and in ascending order (Stationpos2 > Stationpos1). |
Enumeration name: |
StepAccelerationRange |
Enumeration value: |
58 |
Description: |
The acceleration of a step is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stIndexed.stStepMove.lrAcc is outside its value range. |
The parameter stMultiBelt.astStation[x].stIndexed.stStepMove.lrAcc must be in the range between Gc_lrMinAcceleration and the smallest MaxAcc. |
Enumeration name: |
StepDecelerationRange |
Enumeration value: |
59 |
Description: |
The deceleration of a step is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stIndexed.stStepMove.lrDec is outside its value range. |
The parameter stMultiBelt.astStation[x].stIndexed.stStepMove.lrDec must be in the range between Gc_lrMinDeceleration and the smallest MaxAcc. |
Enumeration name: |
StepJerkRange |
Enumeration value: |
60 |
Description: |
The jerk of a step is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stIndexed.stStepMove.lrJerk is outside its value range. |
The parameter stMultiBelt.astStation[x].stIndexed.stStepMove.lrJerk must be in the range > Gc_lrMinJerk. |
Enumeration name: |
StepsRange |
Enumeration value: |
72 |
Description: |
Steps is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].alrSteps[y] is outside its value range. |
The parameter stMultiBelt.astStation[x].alrSteps[y] must be in the range > 0. |
Enumeration name: |
StepVelocityRange |
Enumeration value: |
57 |
Description: |
The velocity for a step is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stIndexed.stStepMove.lrVel is outside its value range. |
The parameter stMultiBelt.astStation[x].stIndexed.stStepMove.lrVel must be in the range between Gc_lrMinVelocity and the smallest MaxVel. |
Enumeration name: |
StopDistanceRange |
Enumeration value: |
75 |
Description: |
StopDistance is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x]. lrStopDistance is outside its value range. |
The parameter stMultiBelt.astStation[x]. lrStopDistance must be in the range >= 0. |
Enumeration name: |
SumOfStepsRange |
Enumeration value: |
73 |
Description: |
The sum of the steps is invalid. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].alrSteps[y] is outside its value range. |
The sum of all steps must be <= stMultiBelt.stGeneral.lrTrainLength. |
Enumeration name: |
SynchronEndRange |
Enumeration value: |
95 |
Description: |
lrSynchronEnd is outside its value range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stSynchron.lrSynchronEnd is outside its value range. |
The parameter stMultiBelt.astStation[x].stSynchron.lrSynchronEnd must be > 0. |
SynchronStartPlusSychronEndEndRange
Enumeration name: |
SynchronStartPlusSychronEndEndRange |
Enumeration value: |
97 |
Description: |
The sum of (SynchronStart + SynchronEnd) is outside its value range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The sum of the parameters (stMultiBelt.astStation[x].stSynchron.lrSynchronStart + iq_stMultiBelt.astStation[x].stSynchron.lrSynchronEnd) is outside their value range. |
The sum of the parameters (stMultiBelt.astStation[x].stSynchron.lrSynchronStart + iq_stMultiBelt.astStation[x].stSynchron.lrSynchronEnd) must be < iq_stMultiBelt.astStation[x].alrSteps[0]. |
Enumeration name: |
SynchronStartRange |
Enumeration value: |
96 |
Description: |
lrSynchronStart is outside its value range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stSynchron.lrSynchronStart is outside its value range. |
The parameter stMultiBelt.astStation[x].stSynchron.lrSynchronStart must be > 0. |
Enumeration name: |
TimerInterfaceInvalid |
Enumeration value: |
35 |
Description: |
The interface Timer is invalid. |
Issue |
Cause |
Solution |
---|---|---|
- |
Timer interface invalid |
Incorrect controller type |
Enumeration name: |
TrainLengthRange |
Enumeration value: |
48 |
Description: |
TrainLength is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.stGeneral.lrTrainLength is outside its value range. |
The parameter stMultiBelt.stGeneral.lrTrainLength must be in the range > 0 to stMultiBelt.stGeneral.lrBeltLength. |
Enumeration name: |
TrainMovesBackward |
Enumeration value: |
39 |
Description: |
A train is moving backwards. |
Issue |
Cause |
Solution |
---|---|---|
- |
The crash monitoring detected a reversing train. |
Verify the parameters. |
Enumeration name: |
TrainOrderInvalid |
Enumeration value: |
31 |
Description: |
The sequence of the trains is invalid. |
Issue |
Cause |
Solution |
---|---|---|
- |
The sequence of the trains is incorrect. |
The trains must be positioned one after the other. The trains must be homed. |
Enumeration name: |
TrainsDistanceFactorRange |
Enumeration value: |
67 |
Description: |
TrainsDistanceFactor is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stIndexed.lrTrainsDistanceFactor is outside its value range. |
The parameter stMultiBelt.astStation[x].stIndexed.lrTrainsDistanceFactor must be in the range >= 0. |
Enumeration name: |
TrainsDistanceRange |
Enumeration value: |
68 |
Description: |
TrainsDistance is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].lrTrainsDistance is outside its value range. |
The parameter stMultiBelt.astStation[x].lrTrainsDistance must be in the range >= 0. |
Enumeration name: |
TrainsPerBeltRange |
Enumeration value: |
45 |
Description: |
TrainsPerBeltRange is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.stGeneral.uiTrainsPerBelt is outside its value range. |
The parameter stMultiBelt.stGeneral.uiTrainsPerBelt must be in the range >= 1. |
Enumeration name: |
TrainTimeOutRange |
Enumeration value: |
77 |
Description: |
TrainTimeOut is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].lrTrainTimeOut is outside its value range. |
The parameter stMultiBelt.astStation[x].lrTrainTimeOut must be in the range >= 0. |
Enumeration name: |
UnknownState |
Enumeration value: |
25 |
Description: |
Indeterminable state. |
Issue |
Cause |
Solution |
---|---|---|
- |
An invalid state occurred during the program processing. |
Contact support |
Enumeration name: |
UserCamIdNotSet |
Enumeration value: |
100 |
Description: |
diUserCamId for the law of motion SystemCam is not assigned. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].stSynchron.diUserCamId is not assigned. |
If stMultiBelt.astStation[x].stSynchron.etLawOfMotion = SystemCam then stMultiBelt.astStation[iStation].stSynchron.diUserCamId must be assigned with a valid CamId. |
Enumeration name: |
WaitAllTrainsInactive |
Enumeration value: |
15 |
Description: |
Wait until all the trains are deactivated. |
Status message - Internal state
Enumeration name: |
WaitAllTrainsReady |
Enumeration value: |
1 |
Description: |
Wait until all the trains are ready. |
Issue |
Cause |
Solution |
---|---|---|
- |
Status message - When activating, the FB waits until all the trains (axes) are in position control. |
The axes have to be activated external. There must be no errors pending. |
Enumeration name: |
WaitAllTrainsStopped |
Enumeration value: |
10 |
Description: |
Wait until all the trains are stopped. |
Issue |
Cause |
Solution |
---|---|---|
- |
Status message - Stop when deactivating the FB. Input i_xEnable = FALSE |
Set input i_xEnable to TRUE. |
Enumeration name: |
WaitColdStartAccepted |
Enumeration value: |
3 |
Description: |
Wait until the cold start has been accepted. |
Status message - Internal state
Enumeration name: |
WaitColdStartDone |
Enumeration value: |
4 |
Description: |
Wait until the cold start is completed. |
Status message - Moving to the cold start position
Enumeration name: |
WaitForStart |
Enumeration value: |
2 |
Description: |
Waiting for starting command. |
Issue |
Cause |
Solution |
---|---|---|
- |
Status message - The function block waits for start. The input i_xStart is FALSE. |
Set the input i_xStart to TRUE. |
Enumeration name: |
WaitStationsReady |
Enumeration value: |
7 |
Description: |
Wait until all the stations are ready. |
Status message - Internal state
Enumeration name: |
WaitWarmStartDone |
Enumeration value: |
6 |
Description: |
Wait until the warm start is completed. |
Status message - Moving to the warm start position.
Enumeration name: |
WarmStartAccelerationRange |
Enumeration value: |
51 |
Description: |
The acceleration for the warm start is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.stGeneral.stWarmStartMove.lrAcc is outside its value range. |
The parameter stMultiBelt.stGeneral.stWarmStartMove.lrAcc must be in the range between Gc_lrMinAcceleration and the smallest MaxAcc. |
Enumeration name: |
WarmStartDecelerationRange |
Enumeration value: |
51 |
Description: |
The deceleration for the warm start is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.stGeneral.stWarmStartMove.lrDec is outside its value range. |
The parameter stMultiBelt.stGeneral.stWarmStartMove.lrDec must be in the range bewteen Gc_lrMinDeceleration and the smallest MaxAcc. |
Enumeration name: |
WarmStartJerkRange |
Enumeration value: |
50 |
Description: |
The jerk for the warm start is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.stGeneral.stWarmStartMove.lrJerk is outside its value range. |
The parameter stMultiBelt.stGeneral.stWarmStartMove.lrJerk must be in the range > Gc_lrMinJerk. |
Enumeration name: |
WarmStartNotPossible |
Enumeration value: |
27 |
Description: |
A warm start is not possible. |
Issue |
Cause |
Solution |
---|---|---|
- |
WarmStart is not possible |
After a serious error detection. No previous cold start. |
Enumeration name: |
WarmStartVelocityRange |
Enumeration value: |
49 |
Description: |
The velocity for the warm start is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.stGeneral.stWarmStartMove.lrVel is outside its value range. |
The parameter stMultiBelt.stGeneral.stWarmStartMove.lrVel must be in the range between Gc_lrMinVelocity and the smallest MaxVel. |
Enumeration name: |
WarningDistanceRange |
Enumeration value: |
76 |
Description: |
Warning distance is outside the valid range. |
Issue |
Cause |
Solution |
---|---|---|
- |
The parameter stMultiBelt.astStation[x].lrWarningDistance is outside its value range. |
The parameter stMultiBelt.astStation[x].lrWarningDistance must be in the range >= 0. |