V3.0.3.0

System Requirements

Using the library with other versions of software or firmware may have results other than described in the present documentation.

Warning_Color.gifWARNING

UNINTENDED EQUIPMENT OPERATION

oBe sure that the software and firmware are of the versions supported by this library.

oContact your Schneider Electric service representative for compatibility information.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Library Information

Version identification

Description

Version

Robotic

V3.0.3.0

Hardware/Firmware Information

EcoStruxure Machine Expert V1.2.6

Version identification

Description

Version

Modicon M262 Motion Controller

(TM262M25MESS8T and TM262M35MESS8T)

V5.0.4.83

Software Information

Version identification

Description

Version

EcoStruxure Machine Expert

V1.2.6

For the related hardware/firmware information, see above.

New Features

The Modicon M262 Motion Controllers TM262M25MESS8T and TM262M35MESS8T are supported now with the following stipulations:

oSercos cycle time must be set to 4 ms.

oOne M262 controller can control one robot.

oThe method IF_RobotConfiguration.SchneiderElectricRobot is not supported.

oThe tracking methods IF_RobotConfiguration.AddLinearTrackingSystem, IF_RobotConfiguration.AddLinearTrackingSystem2, IF_RobotConfigu­ration.AddLinearTrackingSystem3, and IF_RobotConfiguration.AddRotativeTrackingSystem are not supported.

oFor Modicon M262 Motion Controllers: If FB_Robot and/or IF_Robot report a diagnostic message and the axis is in MOIN.ET_AxisState.ErrorStop state, FB_Robot and/or IF_Robot must be disabled and MC_Reset must be executed to reset the axis.

Known Operational Anomalies

For Modicon M262 Motion Controllers with an axis configured as modulo, the property xEnable of FB_Robot does not operate as intended.

If you set xEnable to TRUE a diagnostic message is reported.

Workaround:

1.Disable the robot.

2.Modify the axis from modulo to linear.

3.Enable the robot. Result: A diagnostic message is reported.

4.Disable the robot again.

5.Enable the robot.