FB_RobotSSeries - General Information
Type: |
Function block |
Available as of: |
V2.4.1.0 |
Inherits from: |
This chapter provides information on:
oTask
POU to control a Lexium S Robot.
Central POU to control a Lexium S Robot.
The initialization is performed via the inherited method SERP.FB_RobotSSeriesParameters.InitializeRobot().
The Schneider Electric service team needs an interface to your application to perform maintenance of the robot. To provide this interface, add VIS_ServiceMode as web visualization to your project. For details, refer to Service Mode - Adding the Web Visualization.
q_etDiag |
q_etDiagExt |
Enumeration value |
Description |
---|---|---|---|
OK |
13 |
The drive is successfully prepared. |
|
OK |
11 |
The drives are virtual. |
|
ConfigurationFailed |
14 |
The drive is not prepared. |
|
ExecutionAborted |
80 |
The BrakeCouplingTime is invalid. |
|
ExecutionAborted |
79 |
The BrakeDisconnectionTime is invalid. |
|
ExecutionAborted |
67 |
BrakeIntegrated is invalid. |
|
ExecutionAborted |
78 |
ControllerStopDec is invalid. |
|
ExecutionAborted |
77 |
ControllerStopJerk is invalid. |
|
ExecutionAborted |
72 |
The ControlMode is invalid. |
|
ExecutionAborted |
64 |
The Direction is invalid. |
|
ExecutionAborted |
5 |
The Drive is invalid. |
|
ExecutionAborted |
92 |
DriveStopCurrentLimit is invalid. |
|
ExecutionAborted |
75 |
The EncoderDirection is invalid. |
|
ExecutionAborted |
73 |
The EncoderGearIn is invalid. |
|
ExecutionAborted |
74 |
The EncoderGearOut is invalid. |
|
ExecutionAborted |
68 |
The EncoderRange is invalid. |
|
ExecutionAborted |
65 |
The FeedConstant is invalid. |
|
ExecutionAborted |
62 |
The GearIn is invalid. |
|
ExecutionAborted |
63 |
The GearOut is invalid. |
|
ExecutionAborted |
3 |
The Interface is invalid. |
|
ExecutionAborted |
32 |
The program call is unavailable. |
|
ExecutionAborted |
76 |
The MotorIdentification is invalid. |
|
ExecutionAborted |
66 |
The MotorType is invalid. |
|
ExecutionAborted |
81 |
StaticFriction is invalid. |
|
ExecutionAborted |
31 |
The interval of the task is invalid. |
|
ExecutionAborted |
93 |
UserDefinedStopMode is invalid. |
|
ExecutionAborted |
71 |
The UserDrivePeakCurrent is invalid. |
|
ExecutionAborted |
82 |
ViscousFriction is invalid. |
|
ExecutionAborted |
70 |
The WorkingState is invalid. |
|
ExecutionAborted |
83 |
YOffsetEnable is invalid. |
|
ExecutionAborted |
97 |
The UserMaxVel is invalid. |
Enumeration name: |
BrakeCouplingTimeInvalid |
Enumeration value: |
80 |
Description: |
The BrakeCouplingTime is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter BrakeCouplingTime of the drive is invalid. |
The parameter BrakeCouplingTime has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
BrakeDisconnectionTimeInvalid |
Enumeration value: |
79 |
Description: |
The BrakeDisconnectionTime is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter BrakeDisconnectionTime of the drive is invalid. |
The parameter BrakeDisconnectionTime has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
BrakeIntegratedInvalid |
Enumeration value: |
67 |
Description: |
BrakeIntegrated is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter BrakeIntegrated of the drive is invalid. |
The parameter BrakeIntegrated has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
ControllerStopDecInvalid |
Enumeration value: |
78 |
Description: |
ControllerStopDec is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter ControllerStopDec of the drive is invalid |
The parameter ControllerStopDec has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
ControllerStopJerkInvalid |
Enumeration value: |
77 |
Description: |
ControllerStopJerk is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter ControllerStopJerk of the drive is invalid |
The parameter ControllerStopJerk has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
ControlModeInvalid |
Enumeration value: |
72 |
Description: |
The ControlMode is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter ControlMode of the drive is invalid |
The parameter ControlMode of the drive has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
DirectionInvalid |
Enumeration value: |
64 |
Description: |
The Direction is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter Direction of the drive is invalid |
The parameter Direction of the drive has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
DriveInvalid |
Enumeration value: |
5 |
Description: |
The Drive is invalid. |
An invalid drive has been configured.
Enumeration name: |
DriveNotPrepared |
Enumeration value: |
14 |
Description: |
The drive is not prepared. |
Issue |
Cause |
Solution |
---|---|---|
Drive is not prepared for execution. |
'P-0-1069.0.0' is unavailable in parameter AdditionalIDNListMDT of the drive. |
Write 'P-0-1069.0.0' to parameter AdditionalIDNListMDT of the drive. |
Enumeration name: |
DriveStopCurrentLimitInvalid |
Enumeration value: |
92 |
Description: |
DriveStopCurrentLimit is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter DriveStopCurrentLimitInvalid of the drive is invalid. |
The parameter DriveStopCurrentLimitInvalid of the drive has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
DriveSuccessfulPrepared |
Enumeration value: |
13 |
Description: |
The drive is successfully prepared. |
The drive is successfully prepared for execution.
Enumeration name: |
EncoderDirectionInvalid |
Enumeration value: |
75 |
Description: |
The EncoderDirection is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter EncoderDirection of the drive is invalid |
The parameter EncoderDirection of the drive has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
EncoderGearInInvalid |
Enumeration value: |
73 |
Description: |
The EncoderGearIn is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter EncoderGearIn of the drive is invalid |
The parameter EncoderGearIn of the drive has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
EncoderGearOutInvalid |
Enumeration value: |
74 |
Description: |
The EncoderGearOut is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter EncoderGearOut of the drive is invalid |
The parameter EncoderGearOut of the drive has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
EncoderRangeInvalid |
Enumeration value: |
68 |
Description: |
The EncoderRange is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter EncoderRange of the drive is invalid |
The parameter EncoderRange of the drive has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
FeedConstantInvalid |
Enumeration value: |
65 |
Description: |
The FeedConstant is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter FeedConstant of the drive is invalid |
The parameter FeedConstant of the drive has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
GearInInvalid |
Enumeration value: |
62 |
Description: |
The GearIn is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter GearIn of the drive is invalid |
The parameter GearIn of the drive has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
GearOutInvalid |
Enumeration value: |
63 |
Description: |
The GearOut is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter GearOut of the drive is invalid |
The parameter GearOut of the drive has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
InterfaceInvalid |
Enumeration value: |
3 |
Description: |
The Interface is invalid. |
An incorrect program behavior occurred. An interface is invalid.
Enumeration name: |
MissingProgramCall |
Enumeration value: |
32 |
Description: |
The program call is unavailable. |
Issue |
Cause |
Solution |
---|---|---|
The program call is unavailable. |
The program SR_SlowCyclicExecution is not called in a cyclic task. |
Ensure that the program SR_SlowCyclicExecution is called in a cyclic task. |
Enumeration name: |
MotorIdentification |
Enumeration value: |
76 |
Description: |
The MotorIdentification is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter MotorIdentification of a drive is invalid. |
The parameter MotorIdentification of a drive is different to the MotorIdentification of the other drives of the robot. |
Ensure that the drives used for one robot have the same value for the parameter MotorIdentification. |
Enumeration name: |
MotorTypeInvalid |
Enumeration value: |
66 |
Description: |
The MotorType is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter MotorType of the drive is invalid |
The parameter MotorType of the drive has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
StaticFrictionInvalid |
Enumeration value: |
81 |
Description: |
StaticFriction is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter StaticFriction of the drive is invalid. |
The parameter StaticFriction is <> 0. |
Ensure that the parameter StaticFriction is 0. |
Enumeration name: |
TaskIntervalInvalid |
Enumeration value: |
31 |
Description: |
The interval of the task is invalid. |
Issue |
Cause |
Solution |
---|---|---|
SR_SlowCyclicExecution is called with an invalid task interval. |
The task that calls SR_SlowCyclicExecution has an invalid task interval. |
Ensure that SR_SlowCyclicExecution is called in a task with 10 ms interval. |
Enumeration name: |
UserDefinedStopModeInvalid |
Enumeration value: |
93 |
Description: |
UserDefinedStopMode is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter UserDefinedStopMode of the drive is invalid. |
The parameter UserDefinedStopMode of the drive has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
UserDrivePeakCurrentInvalid |
Enumeration value: |
71 |
Description: |
The UserDrivePeakCurrent is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter UserDrivePeakCurrent of the drive is invalid. |
The parameter UserDrivePeakCurrent of the drive has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
UserMaxVelInvalid |
Enumeration value: |
97 |
Description: |
The UserMaxVel is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter UserMaxVel of the drive is invalid. |
The parameter UserMaxVel of the drive has been adapted. |
See property sMsg for expected value. |
Enumeration name: |
VirtualDrives |
Enumeration value: |
11 |
Description: |
The drives are virtual. |
Drives are virtual.
Enumeration name: |
ViscousFrictionInvalid |
Enumeration value: |
82 |
Description: |
ViscousFriction is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter StaticFriction of the drive is invalid. |
The parameter StaticFriction is <> 0. |
Ensure that the parameter StaticFriction is 0. |
Enumeration name: |
WorkingStateInvalid |
Enumeration value: |
70 |
Description: |
The WorkingState is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter WorkingState of a drive is invalid. |
The parameter WorkingState of a drive is different to the WorkingState of the other drives of the robot. |
Ensure that the drives used for one robot have the same value for the parameter WorkingState. |
Enumeration name: |
YOffsetEnableInvalid |
Enumeration value: |
83 |
Description: |
YOffsetEnable is invalid. |
Issue |
Cause |
Solution |
---|---|---|
The parameter YOffsetEnable is invalid. |
YOffsetEnable is active. |
Ensure that the parameter YOffsetEnable is not used. |
Name |
Description |
---|---|
Read the parameter, which influences the control loop of the Lexium S Robot axes. |
|
Read position limits of axes for a Lexium S Robot. |
|
Register the FB_RobotSSeries to the Application Logger. |
|
Set parameter to influence the control loop of the Lexium S Robot axes. |
|
Set position limits of axes for a Lexium S Robot. |
Name |
Description |
---|---|
Initialize the robot and its axes. |
Name |
Data type |
Accessing |
Description |
---|---|---|---|
etDiag |
Read |
General library-independent statement of the diagnostic. A value unequal to GD.ET_Diag.Ok corresponds to a diagnostic message. |
|
etDiagExt |
Read |
POU-specific output on the diagnostic. q_etDiag = GD.ET_Diag.Ok -> Status message q_etDiag <> GD.ET_Diag.Ok -> Diagnostic message |
|
ifCalibration |
Read |
Get the interface to execute calibration modes. |
|
ifSchneiderElectricRobot |
ROB.IF_SchneiderElectricRobot |
Read |
Get the interface for the configuration method ROB.IF_RobotConfiguration.SchneiderElectricRobot |
sMsg |
STRING[80] |
Read |
Event-triggered message that gives more detailed information on the diagnostic state. |
xAxesConfigured |
BOOL |
Read |
TRUE: The axes have been configured successfully. |
xDiagQuit |
BOOL |
Read/write |
A rising edge FALSE->TRUE acknowledges diagnostic messages. |
xDisableWorkEnvelopeMoveCmds |
BOOL |
Read/write |
Disable the checks that are done with a move command TRUE: Disable the verification when sending move commands to the robot. Default value: FALSE In case of xDisableWorkEnvelopeMoveCmds activated and the robot is outside the work envelope, the robot accepts the move commands and returns ET_Diag = Ok. The robot starts the movement but will immediately stop. |