CavtProt: Cavitation Protection
This section describes the CavtProt function block that helps to avoid operating the VS and FS pumps in a cavitation situation. To achieve this, it monitors the suction pressure and adapts the pressure setpoint, if necessary.
NOTE: A pressure sensor providing absolute pressure values is required to implement this function.
NOTICE |
CAVITATION CAUSING INOPERABLE EQUIPMENT |
Select a pressure sensor providing absolute values and make sure to configure the correct NPSH+ value defined by the manufacturer of the pump you are using. |
Failure to follow these instructions can result in equipment damage. |
NOTE: This function block is designed to be used in conjunction with other function blocks of the Pumping Library.