Type: |
Enumeration |
Available as of: |
V1.0.1.0 |
The enumeration ET_StatusAutoTune specifies the status information provided by the auto-tuning algorithm.
Also refer to chapter Auto-Tuning (Heating).
Name |
Data type |
Value |
Description |
---|---|---|---|
Inactive |
INT |
0 |
Auto-tuning not active. (Default value) |
InProgress |
INT |
1 |
Auto-tuning is in progress. |
CompletedSystemOk |
INT |
2 |
Auto-tuning is finished and the system comparison detected a balanced system. |
CompletedSystemOversized |
INT |
3 |
Auto-tuning is finished and the system comparison detected an oversized system. In this case, the calculated PID parameters may not be applicable. Enter parameters manually or execute auto-tuning again with adjusted values. Also refer to System Comparison After Auto-tuning. |
CompletedSystemUndersized |
INT |
4 |
Auto-tuning is finished and the system comparison detected an undersized system. In this case, the calculated PID parameters may not be applicable. Enter parameters manually or execute auto-tuning again with adjusted values. |