Hazardous Location Installation - For USA and Canada
This product has been designed with the intention of meeting the requirements of Class I, Division 2 hazardous location application. Division 2 locations are those locations where ignitable concentrations of flammable substances are normally confined, prevented by ventilation, or present in an adjacent Class I, Division 1 location, but where an abnormal situation might result in intermittent exposure to such ignitable concentrations.
While this product is a non-incendive device under UL 121201 and CSA C22.2 N°213, it is not designed for, and should never be used within a Division 1 (normally hazardous) location.
This product is suitable for use in Class I, Division 2, Groups A, B, C, and D hazardous locations or in non-hazardous locations. Before installing or using this product, confirm that the UL 121201 or CSA22.2 N°213 certification appears on the product labeling.
NOTE: Some products are not yet rated as suitable for use in hazardous locations. Always use your product in conformance with the product labeling and this manual.
|
POTENTIAL FOR EXPLOSION |
oAlways confirm the UL 121201 or CSA C22.2 N°213 hazardous location rating of your device before installing or using it in a hazardous location. oTo apply or remove the supply power from this product installed in a Class I, Division 2 hazardous location, you must either: oUse a switch located outside the hazardous environment, or; oUse a switch certified for Class I, Division 1 operation inside the hazardous area. oDo not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous. This applies to all connections including power, ground, serial, parallel, and network connections. oNever use unshielded / ungrounded cables in hazardous locations. oUse only non-incendive USB devices. oWhen enclosed, keep enclosure doors and openings closed at all times to avoid the accumulation of foreign matter inside the workstation. |
Failure to follow these instructions will result in death or serious injury. |
Make sure that this product is properly rated for the location. If the intended location does not presently have a Class, Division and Group rating, then users should consult the appropriate authorities having jurisdiction in order to determine the correct rating for that hazardous location.
The systems have been designed for compliance with relevant spark ignition tests.
NOTE: IP66F and IP67F are not part of UL certification.