TM5SPDG5D4F Presentation

Main Characteristics

The TM5SPDG5D4F CDM provides 5 x 0 Vdc and 5 x 24 Vdc terminal connections from an external 24 Vdc power source. There is no connection to the 24 Vdc I/O power segment.

The module is equipped with an exchangeable fuse between the 24 Vdc potential on the terminal block and the external 24 Vdc power source. The status of the fuse is available with the status LEDs and in the I/O mapping tab of the EcoStruxure Machine Expert software.

The table below gives you the main characteristics of the TM5SPDG5D4F electronic module:

Main Characteristics

Power supply source

External 24 Vdc power source

Type of common connections

0 Vdc

24 Vdc

Number of common connections

5

5

Ordering Information

The following figure shows a slice with the TM5SPDG5D4F electronic module:

G-SE-0000922.3.gif-high.gif

 

 

Number

Model Number

Description

Color

1

TM5ACBM11

or

TM5ACBM15

Bus base

 

Bus base with address setting

White

 

White

2

TM5SPDG5D4F

Electronic module

White

3

TM5ACTB12

Terminal block, 12-pin

White

NOTE: For more information, refer to TM5 Bus Bases and Terminal Blocks.

Status LEDs

The following figure shows the TM5SPDG5D4F status LEDs:

G-SE-0003206.1.gif-high.gif

 

 

The table below describes the TM5SPDG5D4F status LEDs:

LEDs

Color

Status

Description

r

Green

Off

Module supply not connected

Single flash

Reset state

Flashing

Preoperational state

On

RUN state

e

Red

Off

Ok or no power supply

On

Detected error or reset state

Single Flash

Fuse is blown or missing

Double Flash

Feed voltage too low

e+r

Steady red / single green flash

Invalid firmware