Maximum Number of Tasks

Maximum Number of Tasks

The maximum number of tasks you can define for the Modicon M258 Logic Controller are:

oTotal number of tasks = 20

oCyclic tasks = 4

oFreewheeling tasks = 1

oEvent tasks = 8

oExternal Event tasks = 8

Special Considerations for Freewheeling

A Freewheeling task does not have a fixed duration. In Freewheeling mode, each task scan starts when the previous scan has been completed and after a period of system processing (30% of the total duration of the Freewheeling task). If the system processing period is reduced to less than 15% for more than 3 seconds due to interruptions by other tasks, a system error is detected. For more information, refer to the System Watchdog.

NOTE: You may wish to avoid using a Freewheeling task in a multi-task application when some high priority and time-consuming tasks are running. Doing so may provoke a task Watchdog Timeout. You should not assign CANopen to a freewheeling task. CANopen should be assigned to a cyclic task.