Current Supplied and Consumption Tables on the 24 Vdc I/O Power Segment
The following tables give a synthesis of the current supplied and current consumed on the 24 Vdc I/O power segment by the following TM5 System components:
oCompact I/O
oElectronic modules
The bus bases do not draw current from the 24 Vdc I/O power segment.
The following table gives the current supplied and consumed by the compact I/O on the 24 Vdc I/O power segment:
Reference |
On the 24 Vdc I/O Power Segment |
|||
---|---|---|---|---|
Maximum Current Supplied (mA) |
Current Consumed by the Electronic Module (mA) |
Maximum Current Consumed by the Loads (mA) |
Maximum Current Consumed by the Sensor/Actuator/External Device (mA) |
|
TM5C24D18T |
– |
140 |
9000 |
– |
TM5C12D8T |
– |
80 |
4000 |
2500 |
TM5C24D12R |
– |
165 |
– |
– |
TM5CAI8O8VL |
– |
205 |
– |
– |
TM5CAI8O8CL |
– |
218 |
– |
– |
TM5CAI8O8CVL |
– |
214 |
– |
– |
TM5C12D6T6L |
– |
290 |
3000 |
– |
The following table gives the current supplied and consumed by the electronic modules on the 24 Vdc I/O power segment:
Reference |
On the 24 Vdc I/O Power Segment |
||||
---|---|---|---|---|---|
Maximum Current Supplied (mA) |
Current Consumed by the Electronic Module (mA) |
Maximum Current Consumed by the Loads (mA) |
Maximum Current Consumed by the Sensor/Actuator/External Device (mA) |
||
Digital Input Modules |
TM5SDI2D |
– |
12 |
– |
500 |
TM5SDI2DF |
– |
34 |
– |
500 |
|
TM5SDI4D |
– |
25 |
– |
500 |
|
TM5SDI6D |
– |
37 |
– |
– |
|
TM5SDI12D |
– |
73 |
– |
– |
|
TM5SDI16D |
– |
61 |
– |
– |
|
TM5SDI2A |
– |
– |
– |
– |
|
TM5SDI4A |
– |
– |
– |
– |
|
TM5SDI6U |
– |
– |
– |
– |
|
Digital Output Modules |
TM5SDO2T |
– |
14 |
1000 |
500 |
TM5SDO4T |
– |
20 |
2000 |
500 |
|
TM5SDO4TA |
– |
21 |
4000 |
500 |
|
TM5SDO6T |
– |
30 |
3000 |
– |
|
TM5SDO8TA |
– |
0 |
– |
– |
|
TM5SDO12T |
– |
48 |
6000 |
– |
|
TM5SDO16T |
– |
40 |
8000 |
– |
|
TM5SDO2R |
– |
– |
– |
– |
|
TM5SDO4R |
– |
– |
– |
– |
|
TM5SDO2S |
– |
– |
– |
– |
|
Mixed Input/output Modules |
TM5SDM12DT |
– |
46 |
2000 |
– |
TM5SMM6D2L |
– |
73 |
– |
– |
|
Analog Input Modules |
TM5SAI2L |
– |
33 |
– |
– |
TM5SAI4L |
– |
46 |
– |
– |
|
TM5SAI2H |
– |
50 |
– |
– |
|
TM5SAI4H |
– |
63 |
– |
– |
|
TM5SAI2PH |
– |
46 |
– |
– |
|
TM5SAI4PH |
– |
46 |
– |
– |
|
TM5SAI2TH |
– |
30 |
– |
– |
|
TM5SAI6TH |
– |
38 |
– |
– |
|
TM5SEAISG |
– |
52 |
– |
– |
|
Analog Output Modules |
TM5SAO2L |
– |
46 |
– |
– |
TM5SAO2H |
– |
50 |
– |
– |
|
TM5SAO4L |
– |
63 |
– |
– |
|
TM5SAO4H |
– |
63 |
– |
– |
|
Expert Modules |
TM5SE1IC02505 |
– |
63 |
– |
300 |
TM5SE1IC01024 |
– |
58 |
– |
300 |
|
TM5SE2IC01024 |
– |
63 |
– |
600 |
|
TM5SE1SC10005 |
– |
63 |
– |
300 |
|
TM5SE1IC20005 |
– |
42 |
– |
300 |
|
TM5SE1MISC20005 |
– |
63 |
– |
300 |
|
Transmitter & Receiver Modules |
TM5SBET1 |
0 |
25 |
– |
– |
TM5SBET7 |
0 |
30 |
– |
– |
|
TM5SBER2 |
10000 |
25 |
– |
– |
|
Communication Module |
TM5SE1RS2 |
– |
60 |
– |
– |
Power Distribution Modules (PDM) |
TM5SPS1 |
10000 |
25 |
– |
– |
TM5SPS1F |
6300 |
34 |
– |
– |
|
TM5SPS2 |
10000 |
25 |
– |
– |
|
TM5SPS2F |
6300 |
34 |
– |
– |
|
Interface Power Distribution Module (IPDM) |
TM5SPS3 |
10000 |
25 |
– |
– |
Common Distribution Modules (CDM) |
TM5SPDG12F |
– |
– |
– |
6300 |
TM5SPDD12F |
– |
– |
– |
6300 |
|
TM5SPDG5D4F |
– |
– |
– |
– |
|
TM5SPDG6D6F |
– |
– |
– |
6300 |
|
Dummy Module |
TM5SD000 |
– |
– |
– |
– |